background image

Description of the device 

 

4.4 Accessories 

 

SCALANCE W788-x / W748-1 

24

 

Operating Instructions, 03/2022, A5E03678333-17 

Cables Industrial Ethernet 

 

Component 

Description 

Article number 

IE FC TP cable 

4 x 2 

Industrial Ethernet FastConnect TP standard cable 

GP 4 x 2, TP installation cable CAT6A for 

connection to IE FC RJ45 Plug 4 x 2, 24 AWG 
Sold by the meter 

6XV1878-2A 

 * Available in different lengths 

4.4.4

 

Power supply 

Energy cable 

 

Component 

Description 

Article number 

Energy cable 2 x 

0.75 

Energy cable for connection of signaling contact 

and power supply 24 VDC, stranded wire 2 x 0.75 

mm

2

, trailing type, not assembled 

Sold by the meter 

6XV1812-8A 

Robust Energy 

Cable 4 x 0.75 

Energy cable for connection of power supply 24 

VDC, 4-wire stranded 4 x 0.75 mm

2

, robust, 

flexible, not assembled 
Sold by the meter 

6XV1801-2A 

M12 PLUG-IN 

CABLE 

Flexible plug-in power cable to connect the power 

supply 24 VDC, 4-wire, preassembled with a 4-pin 

M12 plug and an M12 socket (A-coded) 

6XV1801-5D* 

 * Available in different lengths 

Socket 

 

Component 

Description 

Article number 

IE POWER M12 

CABLE 

CONNECTOR 

PRO 

Socket for the 24 VDC power supply. 4-pin, A-

coded 
pack of 3 

6GK1907-0DC10-6AA3 

4.4.5

 

Flexible connecting cables, antennas and accessories 

You will find an overview of the IWLAN products and their accessories in the Order 

overview (

https://support.industry.siemens.com/cs/ww/en/view/109766333

). 

Содержание SIMATIC NET SCALANCE W748-1

Страница 1: ...perating Instructions 03 2022 A5E03678333 17 Introduction 1 Safety notices 2 Security recommendations 3 Description of the device 4 Installation and removal 5 Connecting up 6 Maintenance and cleaning 7 Troubleshooting 8 Technical specifications 9 Dimension drawings 10 Certification 11 ...

Страница 2: ...ly by personnel qualified for the specific task in accordance with the relevant documentation in particular its warning notices and safety instructions Qualified personnel are those who based on their training and experience are capable of identifying risks and avoiding potential hazards when working with these products systems Proper use of Siemens products Note the following WARNING Siemens prod...

Страница 3: ...er supply 24 4 4 5 Flexible connecting cables antennas and accessories 24 4 4 5 1 Flexible connecting cables 25 4 4 5 2 Lightning protection 26 4 4 5 3 Terminating resistor 26 4 4 5 4 Cabinet feedthrough 26 4 4 5 5 Antennas 27 4 5 LED display 29 4 6 Reset button 32 4 7 PLUG 33 5 Installation and removal 37 5 1 Safety notices for installation 37 5 2 Securing the housing 40 5 3 Wall mounting 41 5 4 ...

Страница 4: ...7 Replacing the PLUG 58 7 Maintenance and cleaning 59 8 Troubleshooting 61 8 1 Device configuration with PRESET PLUG 61 8 2 Restoring the factory settings 63 8 3 Firmware update via WBM or CLI not possible 65 9 Technical specifications 67 9 1 SCALANCE W7x8 1 67 9 2 SCALANCE W7x8 2 69 10 Dimension drawings 73 11 Certification 75 Index 77 ...

Страница 5: ...J 45 6GK5748 1FC00 0AA0 6GK5748 1FC00 0AB0 SCALANCE W748 1 M12 6GK5748 1GD00 0AA0 6GK5748 1GD00 0AB0 If information relates to all the named products the term SCALANCE W7x8 will be used These operating instructions apply to the following software version SCALANCE W7x8 with firmware as of version 6 5 Purpose of the Operating Instructions Using the Operating Instructions you will be able to install ...

Страница 6: ...ied with the documentation Security information Siemens provides products and solutions with industrial security functions that support the secure operation of plants systems machines and networks In order to protect plants systems machines and networks against cyber threats it is necessary to implement and continuously maintain a holistic state of the art industrial security concept Siemens produ...

Страница 7: ...re software support Check regularly for new firmware software versions or security updates and apply them After the release of a new version previous versions are no longer supported and are not maintained Device defective If a fault develops send the device to your SIEMENS representative for repair Repairs on site are not possible Decommissioning Shut down the device properly to prevent unauthori...

Страница 8: ... W788 x W748 1 8 Operating Instructions 03 2022 A5E03678333 17 Trademarks The following and possibly other names not identified by the registered trademark sign are registered trademarks of Siemens AG SCALANCE C PLUG RCoax ...

Страница 9: ...e entire working life of the device You should also read the safety notices relating to handling in the individual sections particularly in the sections Installation and Connecting up WARNING Hot surfaces Electric devices have hot surfaces Do not touch these surfaces They could cause severe burns Allow the device to cool down before starting any work on it WARNING EXPLOSION HAZARD Do not open the ...

Страница 10: ...Safety notices SCALANCE W788 x W748 1 10 Operating Instructions 03 2022 A5E03678333 17 ...

Страница 11: ... data transmission via a non secure network use an encrypted VPN tunnel IPsec OpenVPN Separate connections correctly WBM SSH etc Check the user documentation of other Siemens products that are used together with the device for additional security recommendations Using remote logging ensure that the system protocols are forwarded to a central logging server Make sure that the server is within the p...

Страница 12: ...their own authentication between endpoints such as ARP or IPv4 An attacker could use vulnerabilities in these protocols to attack hosts switches and routers connected to your layer 2 network for example through manipulation poisoning of the ARP caches of systems in the subnet and subsequent interception of the data traffic Appropriate security measures must be taken for non secure layer 2 protocol...

Страница 13: ...tional devices with VPN functionality to encrypt and authenticate communication When you establish a secure connection to a server for example for an upgrade make sure that strong encryption methods and protocols are configured for the server Terminate the management connections e g HTTP HTTPS SSH properly Make sure that the device has been powered down completely before you decommission it For mo...

Страница 14: ...onfiguration files are adequately protected The options for achieving this include digitally signing and encrypting the files storing them in a secure location or transmitting configuration files only through secure communication channels Configuration files can be password protected during download You enter passwords on the WBM page System Load Save Passwords When using SNMP Simple Network Manag...

Страница 15: ...ed ensure that the device is operated in a protected network area Check whether use of the following protocols and services is necessary Non authenticated and unencrypted ports LLDP Syslog DHCP options 66 67 TFTP Telnet HTTP SNMP v1 2c Syslog SNTP The following protocols provide secure alternatives SNMPv1 v2c SNMPv3 Check whether use of SNMPv1 v2c is necessary SNMPv1 v2c is classified as non secur...

Страница 16: ... The services that the device supports Default port status This is the status of the port in the delivery state factory setting Configurable port service Indicates whether the port number or the service can be configured via WBM CLI Authentication Specifies whether the communication partner is authenticated If optional the authentication can be configured as required Encryption Specifies whether t...

Страница 17: ... TCP 80 Open HTTPS TCP 443 Open NTP Client UDP 123 Outgoing only PROFINET UDP 34964 UDP 49154 UDP 49155 Open RADIUS Client UDP 1812 Outgoing only Remote Capture TCP 2002 Closed SFTP Client TCP 22 Closed SMTP Client TCP 25 Closed SMTP Client secure 1 TCP 465 Closed SNMPv1 v2c UDP 161 Open SNMPv3 UDP 161 Open Optional Optional SNMP Traps UDP 162 Outgoing only SNTP Client UDP 123 Outgoing only SSH TC...

Страница 18: ...be accessed The table includes the following columns Layer 2 service The Layer 2 services that the device supports Default status The default status of the service open or closed Service configurable Indicates whether the service can be configured via WBM CLI Layer 2 service Default status Service configurable DCP Open LLDP Open RSTP Open iPRP Open MSTP Closed SIMATIC NET TIME Closed ...

Страница 19: ...48 1 Operating Instructions 03 2022 A5E03678333 17 19 Description of the device 4 4 1 Structure of the type designations The type designation of a SCALANCE W7x8 is made up of several parts that have the following meaning ...

Страница 20: ...e Devices with one IWLAN interface Three connectors on the top covered Devices with two IWLAN interfaces Three connectors on the top covered Three connectors on the bottom shown Connector for power supply Ethernet connector Screw down cover for the Reset button and for the PLUG slot Digital input DI Digital output DQ PLUG slot Reset button Grounding connector thread M4 on the back of the device co...

Страница 21: ...evices with one IWLAN interface Three connectors on the top Devices with two IWLAN interfaces Three connectors on the top Three connectors on the bottom LED display Connector for power supply with cover Ethernet connector with cover Screw down cover for the Reset button and for the PLUG slot PLUG slot Reset button Grounding connector thread M4 on the back of the device covered ...

Страница 22: ...n the scope of delivery see Accessories Please check that the consignment you have received is complete If the consignment is incomplete contact your supplier or your local Siemens office 4 4 Accessories Technical data subject to change You will find further information on the range of accessories in the Industry Mall https mall industry siemens com Use the TIA Selection Tool https mall industry s...

Страница 23: ...ector Industrial Ethernet For the M12 variants the following plug in connector is required Component Description Article number IE FC M12 PLUG PRO 4 x 2 Industrial Ethernet FastConnect M12 Plug PRO 4 x 2 M12 plug in connector with rugged metal housing and FC connector technology with axial cable outlet X coded 1 connector per package 6GK1901 0DB30 6AA0 8 connectors per package 6GK1901 0DB30 6AA8 F...

Страница 24: ...m2 trailing type not assembled Sold by the meter 6XV1812 8A Robust Energy Cable 4 x 0 75 Energy cable for connection of power supply 24 VDC 4 wire stranded 4 x 0 75 mm2 robust flexible not assembled Sold by the meter 6XV1801 2A M12 PLUG IN CABLE Flexible plug in power cable to connect the power supply 24 VDC 4 wire preassembled with a 4 pin M12 plug and an M12 socket A coded 6XV1801 5D Available i...

Страница 25: ...6XV1875 5TH10 2 m 6XV1875 5TH20 5 m 6XV1875 5TH50 Flexible connecting cable N Connect N Connect Flexible connecting cable for connecting an antenna to a SCALANCE W device with N Connect connectors preassembled with two N male connectors Length Article number 1 m 6XV1875 5AH10 2 m 6XV1875 5AH20 5 m 6XV1875 5AH50 10 m 6XV1875 5AN10 For railway applications the following connecting cable are availabl...

Страница 26: ...r Component Description Article number TI795 1N Electrical connection N Connect male 6GK5795 1TN00 1AA0 TI795 1R Electrical connection RSMA Connect male 6GK5795 1TR10 0AA6 4 4 5 4 Cabinet feedthrough Cabinet feedthrough Component Description Article number IE M12 PANEL FEEDTHROUGH 4 x 2 Cabinet feedthrough for conversion from M12 connector technology X coded IP65 67 to RJ 45 connector technology X...

Страница 27: ...x N Connect female 6GK5793 8DJ00 0AA0 ANT793 8DK Directional antenna mast wall mounting 23 dBi 5 GHz 2 x N Connect female 6GK5793 8DK00 0AA0 ANT793 8DL Directional antenna vertical horizontal polarized 5 GHz 14dBi IP66 2 x N Connector female 6GK5793 8DL00 0AA0 ANT793 8DP Directional antenna mast wall mounting 13 13 5 dBi 4 9 GHz and 5 GHz N Connect female This antenna is not available in Korea 6GK...

Страница 28: ...mnidirectional antenna 5 7 dBi 2 4 GHz and 5 GHz IP65 67 N Connector female 6GK5795 6MP00 0AA0 IWLAN RCoax Cable 2 4 GHz PE 1 2 Omnidirectional antenna 0 Bi 2 400 2 485 GHz N Connect female 6XV1875 2A IWLAN RCoax Cable 5 GHz PE 1 2 Omnidirectional antenna 0 Bi 5 150 5 875 GHz N Connect female 6XV1875 2D NOTICE ANT795 4MA The ANT795 4MA antenna has degree of protection IP30 and is therefore only su...

Страница 29: ...SCALANCE W7x8 LEDs with RJ 45 variants LEDs with M12 variants Note The R2 LED only exists on devices with two IWLAN interfaces LED Color Meaning L1 Off Power supply L1 too low Green Power supply L1 is applied L2 1 Off Power supply L2 too low Green Power supply L2 is applied PoE Off The device is not supplied using PoE Green The device is supplied using PoE P1 Off There is no connection over the Et...

Страница 30: ...int mode With DFS 802 11h the channel is scanned for one minute for competing radar signals before the channel can be used for data traffic Client mode The client waits for the MAC address due to the setting Automatic for the MAC mode parameter and is not connected to an access point Flashing yellow and green Interval 3x 100 ms on 100 ms off 1x 1000 ms on Client mode The client waits for the MAC a...

Страница 31: ...red Flashing red Interval 500 ms on 500 ms off The bootloader waits in this state for a new firmware file that you can download by TFTP Flashing red Interval 2000 ms on 200 ms off Firmware on PLUG The device is performing a firmware update or downgrade Red Simultaneous R1 R2 yellow flashing A competing radar signal was found on all enabled channels P1 R1 R2 Flashing yellow The port LEDs flash for ...

Страница 32: ...irements and cannot be shortened even by restarting the device 4 6 Reset button Position NOTICE Loss of the degree of protection When the cover is not mounted correctly the device loses its degree of protection The Reset button is located behind the screw down cover on the underside of the housing see Device description Page 21 Functions The reset button has the following functions Restart of the ...

Страница 33: ...es and failures in the configured network with further consequences 4 7 PLUG The PLUG is available in the following variants C PLUG The removable data storage medium only saves the configuration data of the device KEY PLUG In addition to the configuration data the removable data storage medium contains a license with which special functions are enabled e g iFeatures You will find the article numbe...

Страница 34: ...tion already existing on the device is automatically stored on the inserted PLUG If the PLUG contains a license additional functions are also enabled A device with a written and accepted PLUG ACCEPTED status uses the configuration data of the PLUG automatically when it starts up Acceptance is possible only when the data was written by a compatible device type One exception to this can be the IP co...

Страница 35: ...tion to reformat the PLUG Note Incompatibility with previous versions with PLUG inserted During the installation of a previous version of the firmware the configuration data can be lost In this case the device starts up with the factory settings after the firmware has been installed In this situation if a PLUG is inserted in the device following the restart this has the status NOT ACCEPTED since t...

Страница 36: ...Description of the device 4 7 PLUG SCALANCE W788 x W748 1 36 Operating Instructions 03 2022 A5E03678333 17 ...

Страница 37: ... risk of explosion in hazardous areas For proper disassembly observe the following Before starting work ensure that the electricity is switched off Secure remaining connections so that no damage can occur as a result of disassembly if the system is accidentally started up CAUTION Minimum distance to antennas Fit the device so that there is a minimum clearance of 20 cm between antennas and persons ...

Страница 38: ...uitability for Class 1 Division 2 or Zone 2 WARNING The device may only be operated in an environment of contamination class 1 or 2 see EN IEC 60664 1 GB T 16935 1 Notes for use in hazardous locations according to ATEX IECEx UKEX and CCC Ex If you use the device under ATEX IECEx UKEX or CCC Ex conditions you must also keep to the following safety instructions in addition to the general safety inst...

Страница 39: ...orresponds to the ambient temperature of the module Use cables with a maximum permitted operating temperature of at least 20 C higher than the maximum ambient temperature WARNING Wall mounting is only permitted if the requirements for the housing the installation regulations the clearance and separating regulations for the control cabinets or housings are adhered to The control cabinet cover or ho...

Страница 40: ...n There are no restrictions regarding the installation location for the device Antennas in particular directional antennas must be mounted according to their characteristics Additional notes For operation outdoors use the SCALANCE W786 The minimum distance to fluorescent lamps should be 0 5 m When installed in a cabinet we recommend that you do not install relays on the same or on directly neighbo...

Страница 41: ...22 A5E03678333 17 41 5 3 Wall mounting Use the holes in the housing to screw the device to the wall or on a horizontal surface The location of the drill holes can be seen in the following figure The following dimensions are specified in mm Ground connector thread M4 Figure 5 1 Drilling template ...

Страница 42: ...A5E03678333 17 5 4 Installing on the S7 300 standard rail Follow the steps below to install the SCALANCE W7x8 on a vertical S7 300 rail 1 Place the device on the upper edge of the S7 300 standard rail position A 2 Screw the device to the rail using the supplied screw position B Figure 5 2 Installing on an S7 300 standard rail ...

Страница 43: ...678333 17 43 5 5 Installing on the S7 1500 standard rail Follow the steps below to install the SCALANCE W7x8 on a vertical S7 1500 rail 1 Place the device on the upper edge of the S7 1500 standard rail position A 2 Screw the device to the rail using the supplied screw position B Figure 5 3 Installing on an S7 1500 standard rail ...

Страница 44: ...ounting on 35 mm DIN EN 50022 rails Mounting adapter for DIN rail Note The mounting adapter for installation on a DIN rail is not included in the scope of delivery see Accessories Page 23 The mounting adapter consists of the following parts 1 DIN rail slider 1 spring 2 screws Mount the mounting adapter on the rear of the device as shown in the figure below Figure 5 4 Fitting the DIN rail slider ...

Страница 45: ...on the DIN rail The following figure shows the SCALANCE W7x8 mounted on a DIN rail Follow the steps outlined below 1 Place the device on the upper edge of the DIN rail position A 2 Pull the spring mounted DIN rail slider position B down and press the device against the DIN rail until it locks in place Figure 5 5 Installing on a DIN rail ...

Страница 46: ...Installation and removal 5 6 Installing on a DIN rail SCALANCE W788 x W748 1 46 Operating Instructions 03 2022 A5E03678333 17 ...

Страница 47: ...ening torque at least 0 4 Nm to achieve the specified type of protection Lightning protection WARNING Danger due to lightning strikes Antennas installed outdoors must be within the area covered by a lightning protection system Make sure that all conducting systems entering from outdoors can be protected by a lightning protection potential equalization system When implementing your lightning protec...

Страница 48: ...nts of EN61000 4 5 surge immunity tests on power supply lines are met only when a Blitzductor is used with 24 VDC BVT AVD 24 article number 918 422 Manufacturer DEHN SÖHNE GmbH Co KG Hans Dehn Str 1 Postfach 1640 D 92306 Neumarkt Germany Supply voltage WARNING Power supply The device is designed for operation with a directly connectable safety extra low voltage SELV from a limited power source LPS...

Страница 49: ...e event of a fault NOTICE Damage to the device due to potential differences To fully eliminate the influence of electromagnetic interference the device must be grounded There must be no potential difference between the following parts otherwise the device or other connected device could be severely damaged Housing of the SCALANCE W device and the ground potential of the antenna Housing of the SCAL...

Страница 50: ...al connections Check the cables for a tight fit after installation WARNING Lack of equipotential bonding If there is no equipotential bonding in hazardous areas there is a risk of explosion due to equalizing current or ignition sparks Ensure that equipotential bonding is available for the device WARNING Unprotected cable ends There is a risk of explosion due to unprotected cable ends in hazardous ...

Страница 51: ...tions for protection against explosion WARNING Suitable cables at high ambient temperatures in hazardous area At an ambient temperature of 60 C use heat resistant cables designed for an ambient temperature at least 20 C higher The cable entries used on the enclosure must comply with the IP degree of protection required by EN IEC IEC 60079 0 GB 3836 1 WARNING Transient overvoltages Take measures to...

Страница 52: ...ment is suitable for use in Class I Zone 2 Group IIC or non hazardous locations only 6 2 Power supply SCALANCE W7x8 x RJ45 IP30 degree of protection The power supply is connected using a 4 pin plug in terminal block that has the following pin assignment Pin Contact Assignment 1 L1 24 VDC 2 M1 Ground 3 M2 Ground 4 L2 24 VDC SCALANCE W7x8 x M12 IP65 degree of protection The power supply is connected...

Страница 53: ...ernative B according to IEEE 802 3af Note Disabling the PoE power supply Before you pull a plug via which the device is supplied with power using PoE disable the relevant PoE power supply Note No power sourcing equipment PSE The W7x8 cannot be used as a PoE power supply for other devices 6 3 Ethernet For connection to Industrial Ethernet the device has either an M12 interface or an RJ45 interface ...

Страница 54: ... interface W7x8 1 have 3 antenna sockets on the top of the device Variants with two IWLAN interfaces W788 2 have 6 antenna sockets 3 on the top and 3 on the underside of the device NOTICE R SMA antenna connector When securing antennas to the device only the screw cap see figure of the antenna can be rotated Rotating the entire antenna could damage the R SMA connector of the device R1A1 R1A2 R1A3 R...

Страница 55: ...he device Note Cabinet installation When installing the SCALANCE W7x8 in a cabinet you need to use detached antennas A suitable flexible connecting cable for a connection between SCALANCE W7x8 and a detached antenna are available from SIMATIC NET You will find detailed information in the section Flexible connecting cables antennas and accessories Page 24 Note If both interfaces of access points wi...

Страница 56: ... 22 The antennas R1A1 and R2A1 must always be connected as soon as the associated WLAN Interface is turned on if no antenna is connected the relevant interface must also be disabled for RX and TX Otherwise there may be transmission disruptions You will find information on the configuration of the antennas in the following documents SCALANCE W7x8 SCALANCE W700 configuration manual section Configuri...

Страница 57: ...al input output must not exceed 30 VDC and not fall below 30 VDC otherwise the digital input output will be destroyed The digital input output is connected to a 4 pin plug in terminal block with the following pin assignment Pin Signal Function 1 DQ output Relay 24 VDC 1 A 2 1L output Relay 24 VDC 1 A 3 DI input plus 24 VDC 4 1M ground 6 6 Grounding Grounding The device has a grounding connector on...

Страница 58: ...ide of the device 3 Insert a screwdriver between the front edge of the PLUG and the slot and release the PLUG 4 Remove the PLUG from the slot 5 Screw the cover back onto the device Inserting the PLUG Follow the steps below to insert a PLUG in the device 1 Turn off the power to the device 2 Remove the cover of the PLUG on the underside of the device 3 The housing of the PLUG has a protruding ridge ...

Страница 59: ...e all relevant installation and safety instructions described in the manuals for the device or supplied with the accessories or spare parts CAUTION Hot surfaces Risk of burns during maintenance work on parts with a surface temperature above 70 C 158 F Take appropriate protective measures for example wear protective gloves Once maintenance work is complete restore the touch protection measures NOTI...

Страница 60: ...Maintenance and cleaning SCALANCE W788 x W748 1 60 Operating Instructions 03 2022 A5E03678333 17 ...

Страница 61: ...on user accounts certificates including the corresponding firmware on multiple devices The PRESET PLUG is write protected You configure the PRESET PLUG using the Command Line Interface CLI Creating a PRESET PLUG You create the PRESET PLUG using the Command Line Interface CLI You can create a PRESET PLUG from any PLUG To do this follow the steps outlined below Note Using configurations with DHCP Cr...

Страница 62: ...tion on this in the operating instructions of your device 3 Insert the PRESET PLUG correctly oriented into the slot The PRESET PLUG is correctly inserted when it is completely inside the device and does not jut out of the slot 4 Turn on the power to the device again If there is a different firmware version on the device to be installed compared with that on the PRESET PLUG an upgrade downgrade of ...

Страница 63: ...u format the PRESET PLUG using the Command Line Interface CLI to reset the preset function To do this follow the steps outlined below 1 Start the remote configuration using Telnet CLI and log on with a user with the admin role 2 Switch to the global configuration mode with the command configure terminal 3 You change to the PLUG configuration mode with the plug command 4 Enter the command factorycl...

Страница 64: ...down the button until the red fault LED F stops flashing after approximately 10 seconds and is permanently lit 6 Now release the button and wait until the fault LED F goes off again 7 The device then starts automatically with the factory settings With SINEC PNI Follow the steps below to reset the device parameters to the factory settings with the SINEC PNI 1 Select the device whose parameters you ...

Страница 65: ...ntil the red fault LED F starts to flash after approximately 2 seconds 4 Now release the button The bootloader waits in this state for a new firmware file that you can download by TFTP 5 Connect a PC to the SCALANCE W over the Ethernet interface 6 Assign an IP address to the SCALANCE W with the SINEC PNI 7 Open a DOS box and change to the directory where the file with the new firmware is located a...

Страница 66: ...3 Firmware update via WBM or CLI not possible SCALANCE W788 x W748 1 66 Operating Instructions 03 2022 A5E03678333 17 Once the firmware has been transferred completely to the device the device is restarted automatically ...

Страница 67: ...d Characteristics 802 11abgn PCIe Minicard REF_W700 RadioInterface pdf Technical specifications Data transfer Ethernet transfer rate 10 100 1000 Mbps Wireless transmission rate 1 450 Mbps Wireless standards supported IEEE 802 11a IEEE 802 11b IEEE 802 11g IEEE 802 11h IEEE 802 11n Power supply standards supported Type IEEE 802 3at type 1 802 3af IEEE 802 3at type 2 Power over Ethernet Class Class ...

Страница 68: ...dance 50 Ω nominal Frequency range 2412 2480 MHz 4920 5875 MHz Electrical data Direct 24 VDC supply Supply voltage from terminal block socket 24 V DC safety extra low voltage SELV Permitted range 19 2 to 28 8 VDC Design RJ 45 variants Terminal block 4 terminals M12 variants M12 connectors Properties Not electrically isolated Supply voltage from PoE Supply voltage from terminal block socket 48 VDC ...

Страница 69: ...P30 IP65 Dimensions and weight Dimensions W x H x D RJ 45 variants M12 variants 200 x 158 x 79 mm 200 x 175 2 x 79 mm Weight 1 7 kg Installation options Direct Wall mounting With additional holding plate Mast mounting Mounting on a DIN rail Mounting on an S7 300 standard rail Mounting on an S7 1500 standard rail Mean time between failure MTBF At 40 C ambient temperature 41 years The PoE class depe...

Страница 70: ...supply standards supported Type IEEE 802 3at type 1 802 3af IEEE 802 3at type 2 Power over Ethernet Class Class 4 Attachment to Industrial Ethernet RJ 45 variants Quantity 1 Design RJ 45 jack Properties Half duplex full duplex autocrossover autonegotiation autosensing PoE floating M12 variants Quantity 1 Design M12 socket Properties Half duplex full duplex autocrossover autonegotiation autosensing...

Страница 71: ...riants 16 8 31 2 VDC UL approvals only valid for 19 2 28 8 VDC Design RJ 45 variants Terminal block 4 terminals M12 variants M12 connectors Properties Not electrically isolated Supply voltage from PoE Supply voltage from terminal block socket 48 VDC Permitted range 36 to 57 VDC Design Via RJ 45 jack Properties Electrically isolating Corresponding to IEEE802 3at Insulation resistance 2 MOhms Fusing...

Страница 72: ...e During operation 2 000 m above sea level at max 60 C ambient temperature Contaminant concentration According to IEC 60721 Degree of protection IP code RJ 45 variants M12 variants IP30 IP65 Dimensions and weight Dimensions W x H x D RJ 45 variants M12 variants 200 x 158 x 79 mm 200 x 175 2 x 79 mm Weight 1 7 kg Installation options Direct Wall mounting With additional holding plate Mast mounting ...

Страница 73: ...erating Instructions 03 2022 A5E03678333 17 73 Dimension drawings 10 The following dimensions are specified in mm SCALANCE W7x8 2 RJ45 Figure 10 1 Front view of RJ45 device versions Figure 10 2 Top view of RJ45 device versions ...

Страница 74: ...Dimension drawings SCALANCE W788 x W748 1 74 Operating Instructions 03 2022 A5E03678333 17 SCALANCE W7x8 2 M12 Figure 10 3 Front view of M12 device versions Figure 10 4 Top view of M12 device versions ...

Страница 75: ...unction at Siemens Industry Online Support https support industry siemens com cs ww en Using the search function at Industrial communication https support industry siemens com cs ww en ps 15859 man Enter the entry ID of the relevant manual as the search item You will find the documentation for the SIMATIC NET products relevant here on the data storage medium that ships with some products Product C...

Страница 76: ...Certification SCALANCE W788 x W748 1 76 Operating Instructions 03 2022 A5E03678333 17 ...

Страница 77: ...57 Dimension drawings 73 Documentation on the CD 5 Documentation on the Internet 6 E Ethernet 53 F Factory defaults 33 63 Factory setting 63 G Grounding 49 57 I Installation DIN rail 44 S7 1500 standard rail 43 S7 300 standard rail 42 Wall mounting 41 Interfaces 67 70 L LED display 29 Lightning protection 47 Loading firmware 32 M Mounting adapter DIN rail 23 P PLUG replacing 58 Power over Ethernet...

Страница 78: ...x W748 1 78 Operating Instructions 03 2022 A5E03678333 17 Scope of delivery 22 SELV 47 Service Support 6 Supply voltage 48 T Technical specifications 67 SCALANCE W788 2 69 SCALANCE W7x8 1 67 Training 6 Type designations 19 ...

Отзывы: