![Siemens SIMATIC NET RUGGEDCOM RX5000 Скачать руководство пользователя страница 49](http://html.mh-extra.com/html/siemens/simatic-net-ruggedcom-rx5000/simatic-net-ruggedcom-rx5000_installation-manual_1266014049.webp)
Certification
6.1.9 Other Approvals
6.1.9
Other Approvals
This device meets the requirements of the following additional standards:
•
IEEE 1613
IEEE Standard Environmental and Testing Requirements for Communications
Networking Devices in Electric Power Substations
•
IEC 61850-3
Communications Networks and Systems for Power Utility Automation – Part 3:
General Requirements
•
IEC 61000-6-2
Electromagnetic Compatibility (EMC) – Part 6-2: Generic Standards – Immunity
for Industrial Environments
6.2
EMC and Environmental Type Tests
The RUGGEDCOM RX5000 has passed the following EMC and environmental tests.
IEC 61850-3 EMC Type Tests
Test
Description
Test Levels
Severity
Levels
Enclosure Contact
+/- 8 kV
4
IEC 61000-4-2
ESD
Enclosure Air
+/- 15 kV
4
IEC 61000-4-3
Radiated RFI
Enclosure Ports
20 V/m
Note
Signal ports
+/- 4 kV @ 2.5 kHz
Note
DC Power ports
+/- 4 kV
4
AC Power ports
+/- 4 kV
4
IEC 61000-4-4 Burst (Fast Transient)
Earth ground ports
+/- 4 kV
4
Signal ports
+/- 4 kV line-to-earth,
+/- 2 kV line-to-line
4
DC Power ports
+/- 2 kV line-to-earth,
+/- 1 kV line-to-line
3
IEC 61000-4-5
Surge
AC Power ports
+/- 4 kV line-to-earth,
+/- 2 kV line-to-line
4
Signal ports
10 V
3
D.C Power ports
10V
3
AC Power ports
10V
3
IEC 61000-4-6
Induced
(Conducted) RFI
Earth ground ports
10V
3
100 A/m
IEC 61000-4-8
Magnetic Field
Enclosure Ports
1000 A/m for 1 s
5
IEC 61000-4-29
Voltage Dips
& Interrupts
DC Power ports
30% for 0.1 s, 60% for
0.1 s, 100% for 0.05 s
40
RUGGEDCOM RX5000
Installation Manual, 01/2021, C79000-G8976-1058-13