B8976111/02
AS-i Master Module CP 142-2
4-18
Flag 1
Flag 2
Name
Bit Number
Name
Bit Number
OFFLINE_READY
8
OFFLINE
0
APF
9
RESERVED
1
NORMAL_MODE
10
EEPROM_OK
2
CONFIG_MODE
11
AUTO_ADDR_ENABLE
3
AUTO_ADDR_AVAIL
12
RESERVED
4
AUTO_ADDR_ASSIGN 13
RESERVED
5
LDS_0
14
RESERVED
6
CONFIG_OK
15
RESERVED
7
Meaning of the flags
OFFLINE_READY
The flag is set when the offline phase is active.
APF
This flag is set when the voltage on the AS-i cable is too low.
NORMAL_MODE
This flag is set when the CP is in the normal mode.
CONFIG_MODE
The flag is set in the configuration mode and reset in the protected mode.
AUTO_ADDR_AVAIL
This flag is set when the automatic address programming can be executed
(in other words exactly one AS-i slave is currently out of operation).
AUTO_ADDR_ASSIGN This flag is set when the automatic address programming is possible (in
other words AUTO_ADDR_ENABLE = 1 and there is or was no “incorrect”
AS-i slave connected to the AS-i cable).
LDS_0
This flag is set when an AS-i slave exists with address 0.
CONFIG_OK
This flag is set when the desired (configured) and actual configuration
match.
OFFLINE
This flag is set when the CP is to change to the OFFLINE mode or is
already in this mode.
EEPROM_OK
This flag is set when the test of the internal EEPROM did not detect any
errors.
AUTO_ADDR_ENABLE This flag indicates whether the automatic address programming is enabled
or disabled by the user (0=disabled, 1= enabled).
Содержание SIMATIC NET CP 142-2
Страница 3: ...SIMATIC NET CP 142 2 Manual C79000 B8976 C111 02 ...
Страница 70: ...B8976111 02 AS i Master Module CP 142 2 7 2 ...
Страница 76: ...AS i Master Module CP 142 2 B8976111 02 A 6 ...
Страница 78: ...AS i Master Module CP 142 2 B8976111 02 B 2 ...
Страница 80: ...AS i Master Module CP 142 2 B8976111 02 C 2 ...
Страница 82: ......