B8976111/02
AS-i Master Module CP 142-2
3-15
If the unconfigured slave 15 is then attached to the AS-Interface, the CP 142-2 once again generates
a diagnostic interrupt. The message “module fault” appears in the diagnostic buffer. The delta list
changes to the values below:
MB 107
80
H
MB 108
80
H
MB 109
00
H
MB 110
00
H
After attaching slave 7 to the AS-Interface again, there is still a problem (slave 15). The message
“module fault” appears in the system diagnostic buffer and the delta list has the following values:
MB 107
00
H
MB 108
80
H
MB 109
00
H
MB 110
00
H
After disconnecting slave 15, there is no further problem. The CP 142-2 signals this with a diagnostic
interrupt. The message “module OK” appears in the diagnostic buffer and the delta list is empty:
MB 107
00
H
MB 108
00
H
MB 109
00
H
MB 110
00
H