B8976111/02
AS-i Master Module CP 142-2
2-6
2.1.4 Indicators and Operator Controls on the CP 142-2
Figure 2.5 shows the front panel of the CP 142-2 with its indicators and operator controls.The front
connector for attaching the AS-i cable is at the lower right of the front panel.
To the left of the connector is the SET/DISPLAY button under a screw-on cover.
Figure 2-5 Front View of the CP 142-2
2.1.4.1 Meaning of the Indicators and Operator Controls:
On the front panel of the CP 142-2, there is a line of 8 LEDs. The upper three LEDs are the group
display. The meaning of the lower five LEDs depends on the status of the group display, as follows:
±
If no LED is lit in the group display, the lower five 5 LEDs indicate the status of the CP 142-2
(status display of the CP 142-2). The label to left of the LEDs then applies. The default display is
the status display.
±
If one or more of the LEDs in the group display are it, the lower five LEDs indicate the slaves
detected or active on the AS-Interface (slave display of the CP 142-2); the label to right of the
LEDs then applies.
You can toggle the display with the SET/DISPLAY button. The SET/DISPLAY button is also required
to configure the CP 142-2. If the button is not pressed for approximately 10 minutes, the CP 142-2
automatically switches to the status display.
Содержание SIMATIC NET CP 142-2
Страница 3: ...SIMATIC NET CP 142 2 Manual C79000 B8976 C111 02 ...
Страница 70: ...B8976111 02 AS i Master Module CP 142 2 7 2 ...
Страница 76: ...AS i Master Module CP 142 2 B8976111 02 A 6 ...
Страница 78: ...AS i Master Module CP 142 2 B8976111 02 B 2 ...
Страница 80: ...AS i Master Module CP 142 2 B8976111 02 C 2 ...
Страница 82: ......