2-2
OP37/Pro Equipment Manual
Release 7/98
2.1
Installing the OP37/Pro
The OP37/Pro is suitable for installation in
19” (48,26 cm) cabinets/racks,
front panels of control cabinets and desks.
!
Caution
In order to prevent the operator panel overheating,
–
the unit must not be exposed to direct sunlight (this also prevents the
keyboard sealing film fading)
–
the vent slots on the unit casing must not be covered over when the unit
is in its installed position.
When installing the OP37/Pro, take the following points into account:
–
The temperature inside the OP rises when it is installed on a slant. The
angle of inclination must not exceed 25
°
installing the unit vertically, reduce the maximum ambient temperature,
e.g. by means of additional heat removal facilities (fan).
–
The operator panel must not be installed horizontally since the cooling
principle of the heat pipe would not work any more.
Note
The IP65 enclosure rating of the front panel is only guaranteed if
the seal on the front panel of the OP is properly seated
the OP is correctly installed using the screw clamps supplied.
If you want to change the labeling of the function keys, perform the steps prior
to installing the OP37/Pro as described in Section 2.3.
Plan sufficient space so as to be able to open the OP37/Pro even when it is in-
stalled. For example, when you replace the back-lighting, it must be possible to
swing a plate (refer to Figure 6-3 on page 6-4) through 90
after opening the
OP.
The OP37/Pro has a depth of approximately 330 mm with swung-out plate, as
measured from the front panel.
Use the section bars of the cabinet or rack manufacturer concerned to mount
the OP37/Pro.
Mounting dimensions of the OP37/Pro for a standard 19” cabinet:
Width: 19” (48.26 cm)
height: 7 height modules
The OP/OP front panel is fixed to the frame sections by means of four screws.
Mounting location
and installation
conditions
Before installation
Mounting in 19”
cabinets/rack
Phaysical Installation
Содержание SIMATIC HMI OP37/Pro
Страница 6: ...iv OP37 Pro Equipment Manual Release 7 98 Preface ...
Страница 8: ...6 10 OP37 Pro Equipment Manual Release 7 98 Servicing Maintenance ...
Страница 26: ...3 8 OP37 Pro Equipment Manual Release 7 98 Electrical Installation ...
Страница 54: ...6 10 OP37 Pro Equipment Manual Release 7 98 Servicing Maintenance ...
Страница 60: ...A 6 OP37 Pro Equipment Manual Release 7 98 Technical Data ...
Страница 72: ...Glossary 2 OP37 Pro Equipment Manual Release 7 98 Glos ...