D-10
OP27, OP37 Equipment Manual
Release 05/99
Remedy:
Cause
Message
636
Event message is not configured
Configure event message (–> message num-
ber) fully.
640
Alarm message is not configured
Configure alarm message (–> message
number).
645
Internal error
PLC co-ordination area not receivable during startup.
Press key to restart.
If the fault is not corrected by performing a
restart, please contact the SIMATIC Hot-
line.
649
Internal error
Driver number configured can not be interpreted.
If the fault is not corrected by performing a
restart, please contact the SIMATIC Hot-
line.
650
Missing area pointer.
Configure an area pointer.
653
The configured user version number does not match the
version number stored on the PLC.
Change configuration and retransfer.
655
PLC acknowledgement area does not physically follow
on from the alarm messages area (–> no startup).
657
Configured PLC protocol is not possible.
Use current firmware version or configure
different protocol.
667
Configuration error:
Variable x:
1
Data type is not DB
2
DB number is greater than 15
3
DB length is greater than 1024
4
DW is in data block header
5
Actual value not in send block
6
Setpoint not in receive block
7
Setpoint/actual value not in receive block
8
Initial value not in send block
9
Data type is not DB
10
DB number is greater than 15
11
DB length is greater than 1024
12
DW is in data block header
13
Area is in wrong DB
14
Sum of data blocks too great
x = 1..8: Change the configuration of the
process link and retransfer.
x = 9..13:Change configuration of area
pointer and retransfer
x = 14:
Restrict configuration and re-
transfer.
668
Incorrect configuration.
Meaning of variables:
1: Incompatible PLC types configured
2: No PLC configured
3: Incorrect baud rate configured
Change configuration and retransfer.
669
Too many actual values (> 512) have been configured for
cyclic reading in a screen/variable.
670
Too many variables requested simultaneously.
Lengthen standard clock pulse or configure
fewer variables on screen.
671
Configuration of message variables incompatible. Differ-
ences between configuration and PLC.
Check S7 programs,
check message server configuration,
dif
fi
i
d d
l
d
i
672
Message not configured.
g
g
,
modify configuration and download again.
680
Selection of a recipe not defined in the project.
Select a valid recipe.