D-5
OP27, OP37 Equipment Manual
Release 05/99
Remedy:
Cause
Message
259
Transfer of a data record to the PLC is taking too long.
Example:
PLC is not acknowledging data record or very large data
records are being transferred.
Check PLC program. In the case of large
data records no modifications are necessary
as the function is being processed correctly.
260
Operating mode of PLC does not match the configura-
tion.
Change operating mode of PLC.
261
The data in this data record is no longer consistent and it
can therefore no longer be used.
Edit data record and check that all entries
are correct.
262
Password or query window already in use by another
function.
Complete first function then execute de-
sired function again.
263
Specified remaining buffer space for messages has been
reached!
Configure smaller remaining buffer, delete
event/alarm message buffers.
264
Message buffer overflow.
The overflow messages are printed out if
so specified in the configuration.
265
The number of passwords issued has already reached 50.
You can not enter any more passwords.
If you wish to issue additional passwords,
you must first delete some of the existing
ones.
266
The field configured in the PLC job does not exist.
Change the parameters of the PLC job and
retransfer the configuration.
303
Fault in connection with PLC.
S5: this error may occur when transferring large data
records. In such cases the watchdog is activated.
Check PLC status.
S5: set value in data word 98 to at least
2000.
305
Data block number missing.
Set up data block or change configuration.
306
Incorrect CPU specified under ”PLC –> Parameters”.
Change configuration and retransfer.
307 ...
311
Variable not present on PLC
Check configuration of process link.
316
Active password level insufficient for menu item
Enter password with higher password level.
339
Startup completed.
Communication with PLC has been re-
sumed.
340
Status processing in progress on PU/PC. The OP can not
be used while this is going on.
341
Internal error
With non-Siemens connections: data block error
342
Network node has illegal address.
Max. addresses:
S7-MPI:
32
PROFIBUS-DP:
128
343
You are attempting to edit a variable of a type that can
not be edited in a recipe: currently applies to ARRAY
variables only.
350
PLC is performing initialization. You can not enter any
setpoints during initialization. Scrolling of screens is
possible.
This operating mode may be set by the
PLC programmer.
351
PLC has completed initialization. You can resume enter-
ing setpoints once this message has appeared.
System Messages