9-7
OP27, OP37 Equipment Manual
Release 05/99
Perform the following steps to load a backup of the firmware/configuration
onto the OP:
Step
Action
1
Insert the memory card containing the firmware/configuration in Slot A of
the OP27 or Slot B of the OP37.
2
Restart the OP. The OP is then started up with the firmware/configuration
contained on the memory card.
3
Press the function key, depicted on the right, in the Backup/Re-
store standard screen to call in the Restore function.
The memory contents of the internal flash memory are over-
written by the firmware/configuration contained on the memory
card.
4
Remove the memory card from the OP.
If the function Backup/Restore is added to the insertion point ”Initialization” in
the configuration, the function is called in each time the OP is started up, being
loaded from the memory card. The system then asks whether the internal flash
memory should be overwritten by the data stored on the memory card.
Step
Action
1
Insert the memory card containing the backup into the corresponding slot
of the system.
2
Start the OP.
3
Confirm initiation of the restore function by answering ”OK” at the
prompt.
4
Remove the memory card from the OP.
Restore firmware/
configuration
Automatic
restoring of
firmware/
configuration
Storing and Loading Data