Commissioning
6.6 Quick commissioning
SIMATIC ET 200pro FC-2 converter
88
Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF
6.6.2.5
Identifying motor data
Identify motor data
WARNING
Unexpected machine motion while the motor data identification is in progress
The stationary measurement can turn the motor a number of revolutions. The rotating
measurement accelerates the motor up to the rated speed. Secure dangerous machine
parts before starting motor data identification:
•
Before switching on, ensure that nobody is working on the machine or located within its
working area.
•
Secure the machine's working area against unintended access.
•
Lower suspended loads to the floor.
Requirements
●
You selected a method of motor data identification during quick commissioning, e.g.
measurement of the motor data while the motor is stationary
When quick commissioning is complete, the inverter issues alarm A07991.
●
The motor has cooled down to the ambient temperature.
An excessively high motor temperature distorts the results of motor data identification.
●
The PC and inverter are connected to each other online.
Procedure
1.
Open the control panel.
2.
Assume master control for the inverter.
3.
Set the "Enable signals"