Installation
4-17
Distributed I/O Device ET 200M
EWA-4NEB780600602-06
4.3
Connecting the Bus Connector
The following bus connectors are available:
Up to 12 Mbaud
– Without programming device socket
(6ES7 972-0BA11-0XA0)
– With programming device socket
(6ES7 972-0BB11-0XA0)
Up to 12 Mbaud, angular outgoing cable
– Without programming device socket
(6ES7 972-0BA40-0XA0)
– With programming device socket
(6ES7 972-0BB40-0XA0)
Connecting the Bus Connector
Proceed as follows to connect the bus connector:
1. Plug the bus connector into the IM 153-x.
2. Screw the bus connector tight on the IM 153-x.
3. If the bus connector is at the beginning or the end of a segment, you must
connect the terminating resistor (switch position ”ON”).
Alternatively, you can use the PROFIBUS terminator as an active bus
terminating element.
4. Lay the interconnecting cable(s) to the designated area for the IM 153-x,
placing it (them) to the right of the 24 V DC terminal.
The nodes with a terminating resistor must always be supplied with voltage during
power-up and operation.