Commissioning and Diagnostics
6-36
Distributed I/O Device ET 200M
EWA-4NEB780600602-06
Diagnostic Interrupt of Modules with Analog Outputs
73
H
: Module with analog outputs
Length of the channel-specific diagnosis
Number of channels per module
Bytes x+16 to x+19: are always 00
H
Byte x+13: Assignment for channel/channel group 1 as for byte 12
Byte x+8
7
0
Diagnostic event on the channel/channel group 0 of the module
Diagnostic event on the channel/channel group 1 of the module
1
2
3
Diagnostic event on channel/channel group 3 of the module
4
5
6
:
7
Configuration/parameter assignment error
0
Short-circuit to M
3
Wire break
4
6
Short circuit to L+
2
5
1
Common-mode error
External load voltage
Byte x+11
0
0
Byte x+9
Byte x+10
Byte x+12
Diagnostic events for channel/channel group 0
Byte x+14: Assignment for channel/channel group 2 as for byte 12
Byte x+15: Assignment for channel/channel group 3 as for byte 12
Byte x+4
:
Byte x+7
See Figure 6-11 on page 6-32
Figure 6-15
Structure as of byte x+8 for diagnostic interrupt (analog outputs)
Process Interrupt of the IM 153-2
If the IM 153-2 reports a process interrupt, there is at least one data record
containing messages concerning time-stamped signal changes or special
messages.
The DP master CPU can read the data record(s) and evaluate them with
the 90 ”IM_DRV” FB (see the PCS 7 documentation).
Evaluation with FB 62 ”FB TIMESTMP” is also possible.