Commissioning
SIMATIC - EM 300 Motor Starters
3-2
GWA-4NEB 640070302-05
3.1
Motor Starters EM 300 DS and EM 300 RS
3.1.1
Commissioning
Set current I
e
Before you commission the motor starter, you must set the current I
e
for trip-
ping the overload release.
External short-circuit protection
If the short-circuit current at the point at which the motor starter is installed is
greater than the rated ultimate short-circuit breaking capacity of the circuit-
breaker (see table), you must provide external short-circuit protection (fuse or
circuit-breaker; see Catalog).
Overload release test
You can test the overload release function.
Reversing starter EM 300 RS
When switching over from right to left or back again, a stop interval of more
than 200 milliseconds must be observed. This interval has to be set via the user
program.
Step
Procedure
1
Open the transparent cover in the top section of the motor starter.
2
Set the current I
e
on the circuit-breaker scale with a screw-driver
(see figure on page 1-2).
U
e
I
cu max
400 V AC
50 kA
440 V AC
10 kA
500 V AC
3 kA
Step
Procedure
1
Open the transparent cover in the top section of the motor starter.
2
Reset the toggle switch from 0 to 1.
3
Insert a screwdriver in the test opening (see figure on page 1-2) and
press it over to the left.
The overload release function is working if the toggle switch is switched
back from 1 to 0.
Содержание SIMATIC EM 300
Страница 40: ...Commissioning SIMATIC EM 300 Motor Starters 3 12 GWA 4NEB 640070302 05 ...
Страница 46: ...Hand held Controller SIMATIC EM 300 Motor Starters 4 6 GWA 4NEB 640070302 05 ...
Страница 58: ...SIGUARD Safety Integrated SIMATIC EM 300 Motor Starters 6 4 GWA 4NEB 640070302 05 ...
Страница 64: ...Dimension Drawings SIMATIC EM 300 Motor Starters B 2 GWA 4NEB 640070302 05 ...
Страница 70: ...Selection Help SIMATIC EM 300 Motor Starters D 4 GWA 4NEB 640070302 05 ...
Страница 72: ...SIMATIC EM 300 Motor Starters Index 2 GWA 4NEB 640070302 05 ...
Страница 74: ...GWA 4NEB 640070302 05 ...