Configuration Frame
SIMATIC - EM 300 Motor Starters
C-2
GWA-4NEB 640070302-05
Byte assignment
The diagram below shows the byte for the input and output signals. Bits X.4 to
X.7 have no meaning.
Evaluation
The following is an extract from an application for interrogating signals.
The address of the motor starter is 4 in the example.
STL
Description
.
Custom application
.
UN
E 4.3
Has circuit-breaker tripped (E4)?
SPB Error
If so, branch to error handling
U
E 4.0
Interrogate operating mode (E1)
SPBN
Branch if manual
.
Program section for driving clockwise
.
rotation output
S
A 4.0
Activate clockwise rotation output(A1)
U
A 4.0
Generate positive edge for timer 0
L
S5T#60ms Load delay time until contactor ”safely on”
U
T0
If timer 0 expires
SPB On
Label:
.
Continue here if time not elapsed
.
Remainder of Program
Ende: BE
On:
UN
E 4.1
Interrogate feedback from contactor (E2)
SPBN Error
Branch if error
SPA Label
Manual: .
Program section for manual mode
.
SPA End
Error:
.
Program section for error handling
.
SPA End
Byte X
X.3
X.0
Input signal DI0 or output signal DO0
Input signal DI1 or output signal DO1
Input signal DI2 or output signal DO2
Input signal DI3 or output signal DO3
Bit no.
Содержание SIMATIC EM 300
Страница 40: ...Commissioning SIMATIC EM 300 Motor Starters 3 12 GWA 4NEB 640070302 05 ...
Страница 46: ...Hand held Controller SIMATIC EM 300 Motor Starters 4 6 GWA 4NEB 640070302 05 ...
Страница 58: ...SIGUARD Safety Integrated SIMATIC EM 300 Motor Starters 6 4 GWA 4NEB 640070302 05 ...
Страница 64: ...Dimension Drawings SIMATIC EM 300 Motor Starters B 2 GWA 4NEB 640070302 05 ...
Страница 70: ...Selection Help SIMATIC EM 300 Motor Starters D 4 GWA 4NEB 640070302 05 ...
Страница 72: ...SIMATIC EM 300 Motor Starters Index 2 GWA 4NEB 640070302 05 ...
Страница 74: ...GWA 4NEB 640070302 05 ...