Commissioning
SIMATIC - EM 300 Motor Starters
3-6
GWA-4NEB 640070302-05
3.2
Motor Starters EM 300 EDS and EM 300 ERS
3.2.1
Commissioning
Set current I
e
Set current I
e
for overload tripping before commissioning the motor starter
EM 300 EDS/ERS. The setting is made with 2 rotary encoder switches with 8 or
10 switch positions (see figure on page 1-3). The set value in each case is deri-
ved from the sum of the two set values.
Set values
The set values together with their position on the rotary encoder switch are
given in the table below
.
Example
If you want to set a current of 1.28 A, turn switch 1 to position 3 and switch 2 to
position 4.
Position of the
rotary encoder
switch
Power range 1
0.6 - 2.18 A
Power range 2
2.0 - 5.95 A
Switch 1
Switch 2
Switch 1
Switch 2
0
0.6
0.00
2.0
0.00
1
0.8
0.02
2.5
0.05
2
1.0
0.04
3.0
0.10
3
1.2
0.06
3.5
0.15
4
1.4
0.08
4.0
0.20
5
1.6
0.10
4.5
0.25
6
1.8
0.12
5.0
0.30
7
2.0
0.14
5.5
0.35
8
—
0.16
—
0.40
9
—
0.18
—
0.45
Power range 1:
1.28 A =
1.2 A +
0.08 A
Switch 1
Position 3
Switch 2
Position 4
Содержание SIMATIC EM 300
Страница 40: ...Commissioning SIMATIC EM 300 Motor Starters 3 12 GWA 4NEB 640070302 05 ...
Страница 46: ...Hand held Controller SIMATIC EM 300 Motor Starters 4 6 GWA 4NEB 640070302 05 ...
Страница 58: ...SIGUARD Safety Integrated SIMATIC EM 300 Motor Starters 6 4 GWA 4NEB 640070302 05 ...
Страница 64: ...Dimension Drawings SIMATIC EM 300 Motor Starters B 2 GWA 4NEB 640070302 05 ...
Страница 70: ...Selection Help SIMATIC EM 300 Motor Starters D 4 GWA 4NEB 640070302 05 ...
Страница 72: ...SIMATIC EM 300 Motor Starters Index 2 GWA 4NEB 640070302 05 ...
Страница 74: ...GWA 4NEB 640070302 05 ...