Technical Specifications
A-3
C7-635 Control System
Mechanical
Environmental Conditions
C7-635 Key
C7-635 Touch
Vibration
Operation
Storage/transport in packaging
Tested in accordance with IEC 60068-2-6
10 to 58 Hz, amplitude 0.075
58 to 150 Hz, acceleration 9.8 m/s
2
5 to 9 Hz, amplitude 3.5 mm
9 to 500 Hz, acceleration 9.8 m/s
Shock test
Operation
Storage/transport
Tested in accordance with IEC 60068-2-29
Half-sine: 150 m/s
2
(15 g), 11 ms, 18 shocks
250 m/s
2
(25 g), 6 ms, 1,000 shocks
Resistance to fire:
Terminal strips
Master strips in housing
FV2 (tested in accordance with IEC 60707)
FV0
A.2
Technical Specifications for TP/OP
The table below summarizes the TP/OP scope of functions for the C7-635. The
values provided for HMI functions are maximum values that can be managed by
the C7-635. These values are limited by the size of the internal configuration
memory and the size of the Compact Flash Card (CF Card) of the TP.
Table A-2 Functional Scope of TP/OP
Function
C7-635 Touch (TP)
C7-635 Key (OP)
Memory
Configuration of the TP
Recipes
768 Kbytes internal
32 Kbytes internal, expandable by means of
Compact Flash Card (CF card)
Operational
Number
400
1)
messages
Display
Message line, message window/
message page, message display
View all pending messages
Message page/message display
Length of message text per
line
70 characters
Process values in message
text
8
Edit message
4
Содержание SIMATIC C7-635
Страница 12: ...Document Guide 1 2 C7 635 Control System A5E00155581 04 ...
Страница 14: ...Product Overview 2 2 C7 635 Control System A5E00155581 04 Figure 2 2 C7 635 Key ...
Страница 48: ...Installing and Wiring the C7 635 3 26 C7 635 Control System A5E00155581 04 ...
Страница 58: ...Special Features of the C7 635 4 10 C7 635 Control System A5E00155581 04 ...