2
2-20
C7-626 / C7-626 DP Control Systems
C79000-G7076-C626-01
2.9
Arrangement of Additional S7-300 Modules
You can connect further S7-300 modules to the C7 via the IM 360 interface
of the C7.
The manual /70/ describes how to install S7-300 modules.
An IM 361 module of the S7-300 system must be connected to the C7.
You can connect an additional I/O as follows:
1. Install the additional I/O as described for racks 1 to 3 in the manual /70/.
2. Connect the C7 to the IM 361 via the IM standard cable (see also
Figure 2-8 for connecting the C7).
When the C7 is first started up, it detects any additional connected modules.
The C7 has an integral IM 360 interface module for I/O expansion with an
external S7 standard I/O. This interface module is characterized by the
following features:
S
Data transmission from the IM 360 to the IM 361 of the first rack
expansion via a 368 connecting cable.
S
Maximum distance between IM 360 and IM 361: 10 m
You can expand your C7 by up to three mounting racks using the IM 360
interface module.
Additional S7-300
Modules
Prerequisite
Connecting
Additional I/Os
IM 360 Interface
Module
Installing and Preparing the C7
Содержание SIMATIC C7-626
Страница 18: ...1 1 6 C7 626 C7 626 DP Control Systems C79000 G7076 C626 01 Product Overview ...
Страница 72: ...3 3 26 C7 626 C7 626 DP Control Systems C79000 G7076 C626 01 Configuring MPI Networks and PROFIBUS DP Networks ...
Страница 78: ...4 4 6 C7 626 C7 626 DP Control Systems C79000 G7076 C626 01 Connecting a Programming Device PC to a C7 ...
Страница 122: ...A A 8 C7 626 C7 626 DP Control Systems C79000 G7076 C626 01 General Technical Specifications ...
Страница 138: ...Glossary 10 C7 626 C7 626 DP Control Systems C79000 G7076 C626 01 Glossary ...
Страница 142: ...Index 4 C7 626 C7 626 DP Control Systems C79000 G7076 C626 01 Index ...