3
3-3
C7-626 / C7-626 DP Control Systems
C79000-G7076-C626-01
You can connect up to 126 (addressable) nodes via the MPI.
To enable all nodes to communicate with each other, you must assign them
an address:
S
In an MPI network, an “MPI address” and a “highest MPI address”.
S
In a PROFIBUS-DP network, an “L2 address” and a “highest L2
address”.
You must assign these MPI/L2 addresses to each node individually with the
programming device before networking (also, with some PROFIBUS-DP
slaves, by using the switch on the slave).
Note
The RS 485 repeater has no “MPI/L2 address”.
Table 3-1 contains all permissible MPI/L2 addresses.
Table 3-1
Permissible MPI/L2 Addresses
MPI Addresses
L2 Addresses
0 to 126
0 to 125
of which reserved:
0 for programming device
1 for C7 OP
2 for C7 CPU
of which reserved:
0 for programming device
The following table shows the default MPI addresses with which the C7
devices are supplied.
Node (Device)
Default
MPI Address
Highest Default
MPI Adress
Programming device
0
15
C7 OP
1
15
C7 CPU
2
15
Number of Nodes
MPI/L2 Addresses
Default MPI
Addresses on the
C7
Configuring MPI Networks and PROFIBUS-DP Networks
Содержание SIMATIC C7-626
Страница 18: ...1 1 6 C7 626 C7 626 DP Control Systems C79000 G7076 C626 01 Product Overview ...
Страница 72: ...3 3 26 C7 626 C7 626 DP Control Systems C79000 G7076 C626 01 Configuring MPI Networks and PROFIBUS DP Networks ...
Страница 78: ...4 4 6 C7 626 C7 626 DP Control Systems C79000 G7076 C626 01 Connecting a Programming Device PC to a C7 ...
Страница 122: ...A A 8 C7 626 C7 626 DP Control Systems C79000 G7076 C626 01 General Technical Specifications ...
Страница 138: ...Glossary 10 C7 626 C7 626 DP Control Systems C79000 G7076 C626 01 Glossary ...
Страница 142: ...Index 4 C7 626 C7 626 DP Control Systems C79000 G7076 C626 01 Index ...