A
A-3
C7-626 / C7-626 DP Control Systems
C79000-G7076-C626-01
Table A-1
Technical Specifications of the C7
Criterion
Technical Specifications
Safety
Standardization
DIN EN 61131-2 IEC 1131-2
Foreign bodies and water protection
S
Device front
S
Device housing
IP 65 to IEC 529
IP 20 to IEC 529
Electromagnetic compatibility (EMC)
Emitted interference
Limit value class
B
in accordance with EN 55022 CISPR 22
Conducted interference on AC
voltage supply lines
±
2kV (in accordance with IEC 801-4/IEC 1000-4-4; burst)
±
1kV (in accordance with IEC 801-5/IEC 1000-4-5;
µ
s pulse / line to line)*
±
2kV (in accordance with IEC 801-5/IEC 1000-4-5;
µ
s pulse / line to
ground)*
*
With protective element lightning conductor KT type AD 24 V from the
Dehn company.
Noise immunity on signal lines
±
2kV (in accordance with IEC 801-4/IEC 1000-4-4; burst)
±
1kV (in accordance with IEC 801-5/IEC 1000-4-5;
µ
s pulse / line to line)*
±
2kV (in accordance with IEC 801-5/IEC 1000-4-5;
µ
s pulse / line to
ground)*
*
With unshielded signal lines with protective element lightning conductor
KT type AD 24 V from the Dehn company.
Noise immunity against discharge
±
6kV, discharge on contact (in accordance with IEC 801-2/IEC 1000-4-2;
ESD)
±
8kV, atmospheric discharge (in accordance with IEC 801-2/IEC 1000-4-2;
ESD)
Immunity to high-frequency
radiation
10V/m with 80% amplitude modulation with 1 kHz,
10kHz-80MHz (in accordance with EN 50 141)
10V/m with 80% amplitude modulation with 1 kHz,
80kHz-1GHz (in accordance with EN 50 140)
10V/m, pulse-modulated, 50 % c.d.f. with 900 MHz (to EN 50 140)
Climatic conditions
Temperature
Operating
Non-operating
Tested in accordance with DIN IEC 68-2-1, DIN IEC 68-2-2
±
0
°
C to +45
°
C
for horizontal installation
±
0
°
C to +50
°
C
for vertical installation
Note:
With forced air ventilation, a maximum of 45
°
C can be obtained
if installed horizontally.
–20
°
C to +70
°
C
Relative humidity
Operating
Non-operating
Tested in accordance with DIN IEC 68-2-3
5% to 95% at 25
°
C (no condensation)
5% to 95% at 25
°
C (no condensation)
Atmospheric pressure
Operating
Non-operating
1080–795 hPa ( –1000m to +2000 m)
1080–660 hPa ( –1000m to +3500 m)
General Technical Specifications
Содержание SIMATIC C7-626
Страница 18: ...1 1 6 C7 626 C7 626 DP Control Systems C79000 G7076 C626 01 Product Overview ...
Страница 72: ...3 3 26 C7 626 C7 626 DP Control Systems C79000 G7076 C626 01 Configuring MPI Networks and PROFIBUS DP Networks ...
Страница 78: ...4 4 6 C7 626 C7 626 DP Control Systems C79000 G7076 C626 01 Connecting a Programming Device PC to a C7 ...
Страница 122: ...A A 8 C7 626 C7 626 DP Control Systems C79000 G7076 C626 01 General Technical Specifications ...
Страница 138: ...Glossary 10 C7 626 C7 626 DP Control Systems C79000 G7076 C626 01 Glossary ...
Страница 142: ...Index 4 C7 626 C7 626 DP Control Systems C79000 G7076 C626 01 Index ...