5.4.2.4 AO-6380
·
Setpoint values by means of currents and voltages
─
Output via analog outputs of a SM-0572
ta
─
Output range settable with a resloution of
ta
−
15 bits + sign at ±20 mA/±10 V
−
Shrinking the range results in decreasing resolution
─
Application functions and procedures according to IEC 60870-5-101/104
ta
−
Formal check
−
Direct command
−
Select and execute command ("select/execute")
─
Adaptation
t
−
Linear (normalized, technologically scaled or short floating point)
t
─
Selectable behavior on communication failure and module failure
ta
(keep value, output substitute value)
─
Spontaneous transmission
t
or
─
Periodical transmission
a