Ambient Conditions
44
SICAM RTUs, SICAM MIC System Description
MC6-054-2.00, Edition 07.2014
4.4.2
Power
Supply
DC
Parameter
Value
Test standard
Cl.
Product stand.
Cl.
Dielectrical test
U
N
≤
60 V (SELV circuit)
1.5 kVeff
2.5 kVeff
1)
IEC 60255-5
IEC 60870-2-1
VW3
IEC 60255-5
Dielectrical test
60 V < U
N
≤
125 V against
SELV-circuits
2.0 kVeff
2.5 kVeff
1)
IEC 60255-5
IEC 60950-1
VW3
IEC 60950-1
Dielectrical test
125 V < U
N
≤
230 V
against SELV-circuits
3.0 kVeff
IEC 60255-5
IEC 60950-1
> VW3
IEC 60950-1
Voltage tolerance DC
+30/-20%
IEC 60870-2-1
IEC 60870-2-1
DC3
IEC 60654-2
>DC3
Voltage ripple DC
£
5%
IEC 60870-2-1
IEC 60870-2-1
VR3
IEC 60654-2
Starting current
S1
IEC 60870-4
IEC 60870-4
S1
Impulse voltage
100/1300µs
1)
normal
1.3 U
N
IEC 61000-4-1
IEC 60870-2-1
Fast transient burst
common
4.0 kVs
IEC 61000-4-4
2)
IEC 60870-2-1
4
IEC 60255-22-4
3
Surge 1.2/50
m
s
common
4.0 kVs
IEC 61000-4-5
IEC 60870-2-1
4
Surge 1.2/50
m
s
normal
4.0 kVs
IEC 61000-4-5
IEC 60870-2-1
>4
Induced HF voltage
10 V
IEC 61000-4-6
Interruption time
£
50 ms
IEC 61000-4-11
IEC 60870-2-1
>1
IEC 60255-11
Ring waves 100 kHz
common
2.5 kVs
IEC 61000-4-12
IEC 60870-2-1
3
IEC 60255-22-1
3
Ring waves 100 kHz
normal
2.5 kVs
IEC 61000-4-12
IEC 60870-2-1
>3
IEC 60255-22-1
3
1)
applies for modules PS-663x
2)
directly connected