5.4.1.2 DI-6102, DI-6103
·
Single-point information
─
Acquisition with a resolution of 1 ms
t
─
Update every 10 ms
a
(in the cycle of the
open-/closed-loop control function
, if larger)
─
Revision
ta
─
Power monitoring
ta
─
Inversion
ta
─
Firmware filter
t
─
Bounce suppression
t
─
Determination of the cause of transmission
t
─
Spontaneous transmission of changes
t
─
Periodical transmission
a
·
Double-point information
─
Acquisition with a resolution of 1 ms
t
─
Update every 10 ms
a
(in the cycle of the
open-/closed-loop control function
, if larger)
─
Revision
ta
─
Power monitoring
ta
─
Inversion
ta
─
Firmware filter
t
─
Bounce suppression
t
─
Monitoring intermediate and faulty positions
t
─
Determination of the cause of transmission
t
─
Reporting switching operations in progress
t
─
Breaker tripping detection
t
─
Breaker tripping suppression during auto-reclose
t
─
Spontaneous transmission of changes
t
─
Periodical transmission
a
·
Integrated totals via count pulses
t1
─
Acquisition by firmware with a maximum count frequency of 20 Hz
−
Pulse length/pause >2 ms/>2 ms
−
Revision
−
Power monitoring
−
Inversion
−
Pulse counting
─
Counter value formation
−
Count pulse evaluation
−
Set counter
─
Formation of integrated totals
−
Counter request
−
Interval control
−
Frozen absolute value
−
Frozen relative value
─
Not power-fail safe
─
Integrated total transmission according to IEC 60870-5-101
─
Spontaneous transmission