System Overview
24
SICAM RTUs, SICAM MIC System Description
MC6-054-2.00, Edition 07.2014
2.3.3.1.1 Configuration Notes
Common Rules
With use of the I/O modules please pay attention to the following notes:
·
Up to 8 I/O-modules can be equipped additionally to the master control module, as long as
─
the total power of the I/O-modules does not exceed 7,0 W
─
the total power of all modules - including supplied modem and bus interface modules -
does not exceed the available power of the power supply module
·
Optional use of the CM-6810 (TM I/O-Modules Extension Cable)
·
AO modules must be equipped at the first slots (up to 3 pieces possible; with 2-line ar-
rangement with CM-6810 only in the first line permitted)
·
The mixture of current and voltage on the same AI module is not possible
·
The mixture of binary information and pulse commands on the same DO module is not
possible
Rules for the Checked Command Output
With use of the option "checked command output" (only with firmware
USIO61
) the following
rules are to be considered:
·
Only 1 command output basic module may be connected, alternatively
─
DO-6220, command output according to
IC1
─
DO-6221, command output according to
RC1
·
The command output via DO-6220 or DO-6221 without a DO-6230 is not possible
·
Up to 7 command output relay modules DO-6230 may be connected
·
The command output via DO-6230 without a DO-6220 or DO-6221 is not possible
·
On a DO-6230 either 1-, or 1.5- or 2-pole impulse commands can be assigned (mixture on
the same module is not permitted)
·
Additionally, further DO module types can be used
·
with paramerization with the SICAM TOOLBOX II, the I/O modules DO-6220, DO-6221
and DO-6230 must be configured underneath the virtual system element
USIO61
Rules for the Return Information to Pulse Command Assignment
With use of the option "return information to pulse command assignment " (only with firmware
USIO61
) the following rules are to be considered:
·
With the parameter-settable assignment the sequence of DI modules and DO modules is
arbitrary
·
With the fixed assignment respectively after a module DI-610
x
a module DO-62
xx
(refer to
5.4.3
,
Return Information to Pulse Command Assignment
) must be equipped
Содержание SICAM MIC
Страница 10: ...Table of Contents 10 SICAM RTUs SICAM MIC System Description MC6 054 2 00 Edition 07 2014 ...
Страница 66: ...System Components and Technical Data 66 SICAM RTUs SICAM MIC System Description MC6 054 2 00 Edition 07 2014 ...
Страница 92: ...Glossary 92 SICAM RTUs SICAM MIC System Description MC6 054 2 00 Edition 07 2014 ...