Data traffic
6.2 Cyclic data traffic
PROFINET Proxy SPP2000
Equipment Manual, 03/2022, L1V30814715D-01
39
6.2.9
Freely available measured variables
The SPP2000 has the following freely available measured variables in addition to the
predefined basic types
Data point PAC2200
Data point PAC3200T
Format
Voltage PH-N L1
Voltage PH-N L1
Float
Voltage PH-N L2
Voltage PH-N L2
Float
Voltage PH-N L3
Voltage PH-N L3
Float
Voltage PH-PH L1-L2
Voltage PH-PH L1-L2
Float
Voltage PH-PH L2-L3
Voltage PH-PH L2-L3
Float
Voltage PH-PH L3-L1
Voltage PH-PH L3-L1
Float
Current L1
Current L1
Float
Current L2
Current L2
Float
Current L3
Current L3
Float
Apparent power L1
Apparent power L1
Float
Apparent power L2
Apparent power L2
Float
Apparent power L3
Apparent power L3
Float
Active power L1
Active power L1
Float
Active power L2
Active power L2
Float
Active power L3
Active power L3
Float
Reactive power L1 (Q1)
Reactive power L1 (Q1)
Float
Reactive power L2 (Q1)
Reactive power L2 (Q1)
Float
Reactive power L3 (Q1)
Reactive power L3 (Q1)
Float
Power factor L1
Power factor L1
Float
Power factor L2
Power factor L2
Float
Power factor L3
Power factor L3
Float
-
THD voltage L1
Float
THD voltage L2
Float
THD voltage L3
Float
THD current L1
Float
THD current L2
Float
THD current L3
Float
Frequency
Frequency
Float
Average voltage PH-N
Average voltage PH-N
Float
Average voltage PH-PH
Average voltage PH-PH
Float
Average current
Average current
Float
Total apparent power
Total apparent power
Float
Total active power
Total active power
Float
Total reactive power (Q1)
Total reactive power (Q1)
Float
Total power factor
Total power factor
Float
Neutral current
Neutral current
Float
-
Amplitude unbalance voltage
Float
Amplitude unbalance current
Float
Limit violations
Unsigned long
Device diagnostics and status
Device diagnostics and status
Unsigned long
Status of digital outputs
Status of digital outputs
Unsigned long
Содержание SENTRON PROFINET Proxy SPP2000
Страница 1: ......
Страница 2: ......
Страница 12: ......
Страница 34: ......
Страница 81: ...PROFINET Proxy SPP2000 Equipment Manual 03 2022 L1V30814715D 01 79 Dimensional drawings 10 ...
Страница 82: ......
Страница 89: ...PROFINET Proxy SPP2000 Equipment Manual 03 2022 L1V30814715D 01 87 ...
Страница 90: ......