Data traffic
6.3 Acyclic data traffic
PROFINET Proxy SPP2000
56
Equipment Manual, 03/2022, L1V30814715D-01
Byte
Length (bits) Format
Description
108
16
Unsigned16
Slot 6 Modbus port
110
16
Unsigned16
Slot 7 device type
112
16
Unsigned16
Slot 7 communication status
114
32
1*char 3*u8
Slot 7 IM0 firmware version
118
32
Unsigned32
Slot 7 IP address
122
16
Unsigned16
Slot 7 Modbus port
124
16
Unsigned16
Slot 8 device type
126
16
Unsigned16
Slot 8 communication status
128
32
1*char 3*u8
Slot 8 IM0 firmware version
132
32
Unsigned32
Slot 8 IP address
136
16
Unsigned16
Slot 8 Modbus port
max. 138
With the "Device type" enumeration, the type of the inserted device can be read out.
Format
Device type
1
SPP2000
2
PAC2200
3
PAC2200MID
4
PAC2200CLP
5
PAC3200T
With the "Communication state" enumeration, the status of the internal communication
between SPP2000 and PAC device can be read out.
Value
Communication state
Description
0x00
DEV_NOT_CONFIGURED
Device is not configured via PLC
0x01
DEV_NOT_CONNECTED
Device is configured but not connected
0x02
DEV_CONNECTED
Device is connected and is checking set/actual
configuration
0x03
DEV_INTEGRATED
Device is connected and configuration is OK
0x10
DEV_IP_PORT_CHG
IP configuration and/or Modbus port modified
Содержание SENTRON PROFINET Proxy SPP2000
Страница 1: ......
Страница 2: ......
Страница 12: ......
Страница 34: ......
Страница 81: ...PROFINET Proxy SPP2000 Equipment Manual 03 2022 L1V30814715D 01 79 Dimensional drawings 10 ...
Страница 82: ......
Страница 89: ...PROFINET Proxy SPP2000 Equipment Manual 03 2022 L1V30814715D 01 87 ...
Страница 90: ......