Description
3.9 Ethernet port
SENTRON PAC3200
Manual, 02/2008, A5E01168664B-04
43
Offset
Number of
registers
Name
Format
Unit
Value range
Access
209
2
Status of the digital inputs*
Unsigned long -
Byte 3 Bit 0 Input 0 R
211
2
Active Tariff
Unsigned long -
0 = Tariff 1
1 = Tariff 2
R
213
2
Working hours counter
Unsigned long s
0 ... 999999999
RW
215
2
Universal counter
Unsigned long -
0 ... 999999999
RW
217
2
Relevant Parameter Changes Counter Unsigned long -
-
R
219
2
Counter All Parameter Changes
Unsigned long -
-
R
221
2
Counter Limit Violations
-
-
-
R
501
2
Demand Active Power - Import
Float
W
-
R
503
2
Demand Reactive Power - Import
Float
var
-
R
505
2
Demand Active Power - Export
Float
W
-
R
507
2
Demand Reactive Power - Export
Float
var
-
R
509
2
Maximum Active Power Reading
during the period
Float
W
-
R
511
2
Minimum Active Power Reading during
the period
Float
W
-
R
513
2
Maximum Reactive Power Reading
during the period
Float
var
-
R
515
2
Minimum Reactive Power Reading
during the period
Float
var
-
R
517
2
Demand Period
Unsigned long s
-
R
519
2
Time Since Start of the active demand
period
Unsigned long s
-
R
801
4
Active Energy Import Tariff 1
Double
Wh
Overflow 1.0e+12
RW
805
4
Active Energy Import Tariff 2
Double
Wh
Overflow 1.0e+12
RW
809
4
Active Energy Export Tariff 1
Double
Wh
Overflow 1.0e+12
RW
813
4
Active Energy Export Tariff 2
Double
Wh
Overflow 1.0e+12
RW
817
4
Reactive Energy Import Tariff 1
Double
varh
Overflow 1.0e+12
RW
821
4
Reactive Energy Import Tariff 2
Double
varh
Overflow 1.0e+12
RW
825
4
Reactive Energy Export Tariff 1
Double
varh
Overflow 1.0e+12
RW
829
4
Reactive Energy Export Tariff 2
Double
varh
Overflow 1.0e+12
RW
833
4
Apparent Energy Tariff 1
Double
VAh
Overflow 1.0e+12
RW
837
4
Apparent Energy Tariff 2
Double
VAh
Overflow 1.0e+12
RW
The following tables contain further details of all measured variables indicated by at least one *.
Abbr. in the "Access" column
Abbreviation
R
Read; read access
W
Write; write access
RW
Read Write; read and write access
Содержание SENTRON PAC3200
Страница 16: ...Introduction 1 6 Further documentation SENTRON PAC3200 16 Manual 02 2008 A5E01168664B 04 ...
Страница 90: ...Connection 6 4 Connection examples SENTRON PAC3200 90 Manual 02 2008 A5E01168664B 04 ...
Страница 124: ...Operator control 8 2 Operator input steps SENTRON PAC3200 124 Manual 02 2008 A5E01168664B 04 ...
Страница 125: ...Operator control 8 2 Operator input steps SENTRON PAC3200 Manual 02 2008 A5E01168664B 04 125 ...
Страница 126: ......
Страница 178: ...Glossary SENTRON PAC3200 178 Manual 02 2008 A5E01168664B 04 ...
Страница 182: ...Index SENTRON PAC3200 182 Manual 02 2008 A5E01168664B 04 ...