
Parameterize
9.2 Parameterizing the operator interface
SENTRON PAC3200
Manual, 02/2008, A5E01168664B-04
135
PT SECONDARY
Secondary voltage. Must be specified if a voltage transformer
is used for measuring.
SENTRON PAC3200 with multi-range power supply
Range: 1 V to 690 V, freely adjustable (max. 600 V for
UL)
Default value: 400 V
SENTRON PAC3200 with extra-low voltage power
supply
Range: 1 V to 500 V, freely adjustable
Default value: 289 V
The property "PT SECONDARY" is only visible, if
"USE PTs?" is set to " ON".
CURRENT INPUT
Figure 9-6
"CURRENT INPUTS" device setting
CAUTION
Please note current carrying capacity
Overload can destroy the SENTRON PAC3200.
When measuring using current transformers, the device must know the current conversion
ratio. For this purpose, the primary and secondary currents must be specified in the fields
"CT PRIMARY" and "CT SECONDARY".
CT PRIMARY
Specify the primary current of the current transformer(s).
Range: 1 A to 99999 A, freely adjustable
Default: 50 A
CT SECONDARY
Specify the secondary current of the current transformer(s).
Range: 1 A, 5 A
Default: 5 A
Содержание SENTRON PAC3200
Страница 16: ...Introduction 1 6 Further documentation SENTRON PAC3200 16 Manual 02 2008 A5E01168664B 04 ...
Страница 90: ...Connection 6 4 Connection examples SENTRON PAC3200 90 Manual 02 2008 A5E01168664B 04 ...
Страница 124: ...Operator control 8 2 Operator input steps SENTRON PAC3200 124 Manual 02 2008 A5E01168664B 04 ...
Страница 125: ...Operator control 8 2 Operator input steps SENTRON PAC3200 Manual 02 2008 A5E01168664B 04 125 ...
Страница 126: ......
Страница 178: ...Glossary SENTRON PAC3200 178 Manual 02 2008 A5E01168664B 04 ...
Страница 182: ...Index SENTRON PAC3200 182 Manual 02 2008 A5E01168664B 04 ...