PROFINET IO
6.3 Metering values, addressing und data traffic
3WA Air Circuit Breaker Communication
60
System Manual, 11/2021, 92310000004-02
Energy data profile e0 Currents
Energy data profile e0 is for integration of the 3WA circuit breaker in the Energy Suite profile.
The predefined data blocks cannot be modified.
Byte
Definition
Default
0...3
Data block 1
Current in phase 1 (float)
4...7
Data block 2
Current in phase 2 (float)
8...11
Data block 3
Current in phase 3 (float)
Energy data profile e1 Total active power
Energy data profile e1 is for integration of the 3WA circuit breaker in the Energy Suite profile.
The predefined data blocks cannot be modified.
Byte
Definition
Default
0...3
Data block 1
Total active power (float)
Energy data profile e2 Energy Basic
Energy data profile e2 is for integration of the 3WA circuit breaker in the Energy Suite profile.
The predefined data blocks cannot be modified.
Byte
Definition
Default
0...3
Data block 1
Total active power (float)
4...7
Data block 2
Total active energy (import) (float)
8...11
Data block 3
Total active energy (export) (float)