![Siemens SENTRON 3WA Скачать руководство пользователя страница 28](http://html.mh-extra.com/html/siemens/sentron-3wa/sentron-3wa_system-manual_375761028.webp)
Status of the circuit breaker
3.10 Activation status of protective functions
3WA Air Circuit Breaker Communication
26
System Manual, 11/2021, 92310000004-02
3.10
Activation status of protective functions
Which protective functions are activated in the circuit breaker can be indicated and evaluated
in the register "Activation status of protective functions".
Protective functions that require a voltage tap have a second data point. This indicates
whether the necessary voltage tap is present.
Example: Protective function "Undervoltage protective function ON" with second data point
"Overvoltage protective function active".
Name
Register (0x0000 HEX)
Activation status of protective functions
0x61E5
Description
Bit
LT protective function ON
0
ST protective function ON
1
MCR protective function ON
2
MCR protective function active
3
INST protective function ON
4
N protective function ON
5
GF REF protective function ON
6
GF UREF protective function ON
7
RC protective function ON
8
Reverse power protective function ON
9
Reverse power protective function active
10
dST protective function ON
11
dST protective function active
12
Undervoltage protective function ON
13
Overvoltage protective function active
14
Underfrequency protective function ON
15
Underfrequency protective function active
16
Overfrequency protective function ON
17
Overfrequency protective function active
18
Current unbalance protective function ON
19
Current unbalance protective function active
20
Voltage unbalance protective function ON
21
Voltage unbalance protective function active
22
Forward power protective function ON
23
Reverse power protective function ON
24
THD voltage protective function ON
25
THD voltage protective function active
26
THD current protective function ON
27
THD current protective function active
28
Phase rotation protective function ON
29
Phase rotation protective function active
30
RC protective function active
31
Содержание SENTRON 3WA
Страница 1: ......
Страница 2: ......
Страница 78: ...Disposal 3WA Air Circuit Breaker Communication 76 System Manual 11 2021 92310000004 02 ...
Страница 82: ......