Configuration
4.4 S7 Distributed Safety
Fail-safe operation of the Mobile Panel 277F IWLAN
68
Function Manual, 08/2008, 6AV6691-1FQ01-2AB0
Inputs
Parameters
Data type Description
Interconnection
RNG_ID
Integer
Click on this input and enter the ID of the
effective range to be monitored by
F_FB_RNG_n. The RNG_ID must be
unique throughout the plant and is set in
WinCC flexible.
---
OVERRIDE
Bool
0 = "Override" mode inactive,
1 = "Override" mode active
Result of the link between
the override switch and the
protection mechanism
MPn_DATA* Word
User data of the inputs of the fail-safe
process image.
PII:
Word 1 = MP_DATA
MPn_RNG*
Word
ID of the effective range in which the HMI
device is located.
PII:
Word 2 = MP_RNG
MPn_F_KEY* Word
Reserved
MPn_STAT*
Word
Data is exchanged with F_FB_MP
through this input/output via
F_DB_STATES.
F_DB_STATES
*MPn is used as follows:
•
With F_FB_RNG_4 for HMI device 1 to HMI device 4
•
With F_FB_RNG_16 for HMI device 1 to HMI device 16
Outputs
Parameters
Data type Description
Interconnection
E_STOP
Bool
Emergency stop
Evaluation of the emergency stop button
of all HMI devices connected to
F_FB_RNG_n.
0 = at least one emergency stop
pressed,
1 = no emergency stop pressed
You can detect if an
emergency stop is pressed
with this output.
GLOB_RD
Bool
Global rampdown
You can detect if a global
rampdown has been
triggered with this output.
LOC_RD
Bool
Local rampdown
You can detect if a local
rampdown has been
triggered with this output.
SHUTDOWN Bool
Shutdown
You can detect if a shutdown
has been triggered with this
output.
ENABLE
Bool
This output passes the state of the
enabling button for the HMI device
logged on in the effective range.
0 = enabling button not presses,
1 = enabling button pressed
You can detect if the
enabling button has been
pressed with this output.