| Types SDV-R and SDV-R-AR distribution circuit breakers
Table 7: Technical ratings
Circuit
breaker
type
Rated
maximum
voltage
Rated withstand
voltages
Rated
short-
circuit and
short-time
current
Rated
interrupting
time
1
Rated
continuous
current
Rated transient
recovery voltage
2
Rated
permissible
tripping
delay time
Y
Rated
closing
and
latching
current
Lightning
impulse
(BIL)
Power
frequency
u
c
TRV
peak
value
t
3
time to
voltage
u
c
kV, rms
kV
3
kV
kA, rms
ms/cycles
A, rms
kV
μs
sec
kA, peak
38.0-25
38.0
200/258
80
25
50/3
1,200,
2,000
71.7
59
2
65
38.0-31.5
38.0
200/258
80
31.5
50/3
1,200,
2,000
71.7
59
2
82
38.0-40
38.0
200/258
80
40
50/3
1,200,
2,000
71.7
59
2
104
Addtional key ratings for SDV-R and
SDV-R-AR:
• Rated closing time <45 ms
• Rated opening time <30 ms
• Rated mechanical switching time
(vacuum circuit breaker open to ground
switch close) 12-16 ms
• Grounding switch rated short-time
current 12.5 kA
• Grounding switch rated closing and
latching current 32.5 kA.
Addtional key ratings for SDV-R-AR:
• Rated accessibility type 2B
• Rated internal arcing short-circuit
current 25, 31.5, or 40 kA
• Rated arcing duration 0.5 s.
Table 8: Control data
Stored-energy operator
Nominal
Range
Close coil
Trip coil
1, 6
Spring charging motor
Close
Trip
A
A
Amperes
run (avg.)
Charging
seconds
125 Vdc
90-140
70-140
2.1
7.4/4.8
4
10
250 Vdc
180-280
140-280
2.1
9.6/4.2
2
10
120 Vac
104-127
104-127
2.0
—
6
10
240 Vac
208-254
208-254
2.0
—
3
10
Footnotes:
1. First value is for standard 50 ms/
three-cycle interrupting time.
Second value is for optional 83
ms/five-cycle interrupting time
2. For stored-energy operator,
power requirement for second
trip coil is approximately 70 W
(dc) or 50 VA (ac). Power
requirement for undervoltage
device is approximately 20 W
(dc) or 20 VA (ac).