Types SDV-R and SDV-R-AR distribution circuit breakers |
Instruction manual
Figure 17: Operator sequential operation diagram
Control voltage
applied.
Undervoltage device
27 picks up.
1
Spring-charge motor
(88) energized.
LS3 opens in series
with anti-pump
relay (52Y).
LS21 and LS22
operate to de-
energize spring-
charging motor (88).
LS41 closes to
signal closing
spring is charged.
LS9 closes close
circuit only when
closing spring is
fully charged.
No action! Open
52b in series with
close coil (52SRC)
blocks closing
spring-release.
Close coil actuated
through closed 52b
contacts and two
normally closed
contacts of the anti-
pump relay (52Y).
Closing
command
when
Circuit
breaker
closed.
Circuit
breaker
open.
No action! Anti-
pump relay (52Y)
picks up through
the closed LS3
contact and opens.
Closing
spring not
charged.
The closing spring
is unlatched.
The opening spring
is charged.
Circuit breaker
auxiliary contacts
52a and 52b
change state.
The circuit breaker
closes and ground
switch opens.
LS21 and LS22
close to energize
motor. LS3 closes
and LS9 opens to
cancel closing
spring signal.
52a contacts in
series with the trip
coil (52T) close to
enable a trip
operation.
Continuous closing
command.
Close coil (52SRC)
unlatches closing spring,
circuit breaker closes, and
ground switch opens.
Motor cutoff switches
LS21, LS22 and LS3 are
closed because the
closing spring is
discharged.
Before the spring-charge
motor has recharged the
closing spring and opened
LS3, anti-pump relay (52Y)
picks up and seals in.
The anti-pump relay (52Y)
opens two contacts in
series with the close coil
(52SRC).
The close coil (52SRC) is
now blocked and cannot
be activated until springs
are fully-charged and close
command is removed.
Rapid auto-reclosing. The closing spring is automatically recharged as described above. Therefore,
when the circuit breaker is closed both of its springs are charged. The closing spring charges the
opening spring during closing. The dashed line shows the operating sequence initiated by the
closing command.
Closing
Tripping
Anti-pumping feature (52Y) assures a continuously applied closing command does not cause the
circuit breaker to reclose automatically after it has tripped out on a fault.
Trip
command.
Trip coil (52T) can
only be activated
when series
connected 52a
contact is closed.
Undervoltage device (27) is
activated by opening a NC
contact in series with 27 or by
loss or reduction of tripping
voltage.
1
Secondary shunt-release
(dual-trip) function
activated by remote trip
command contact NO.
1
Undervoltage device (27) is activated
by closing NO contact, shorting the
27 coil. The NO contact is only
effective with the circuit breaker
closed. Resistor required.
1
Undervoltage device 27
unlatches the opening
spring.
1
Circuit breaker trips and
ground switch closes.
Secondary release
unlatches the opening
spring.
1
Trip coil (52T)
unlatches the
opening spring.
Footnote:
1
Optional items.
Closing spring fully
charged.