54
Types SDV-R and SDV-R-AR distribution circuit breakers |
Instruction manual
Type auxiliary
switch
Continuous
current A
Control circuit voltage
120 Vac
240 Vac
125 Vdc
250 Vdc
Circuit breaker
auxiliary switch
10
Non-inductive circuit interrupting capacity in A
10
5
9.6
4.8
Inductive circuit interrupting capacity in A
6
3
6
3
Table 9: Interrupting capacity auxiliary switch contacts
Location
Heater
wattage
High-voltage compartment
1,200
1
Relay and control compartment
100
1
Operator compartment - stored-energy operator
(for application below -30 °C down to -50 °C)
150
2
Table 11: Space heater data
Footnotes:
1. Thermostat controlled and set to turn off at
95 °F.
2. Thermostat controlled and set to turn off at
10 °F.
Voltage Interrupting
Continuous current
1,200 A
1,2
2,000 A
1,2
Pallet
Seismic
cross braces
38.0 kV
25/31.5/40 kA
5,030
(2,282)
5,525
(2,506)
150
(68)
177
(77)
Table 10: Type SDV-R distribution circuit breaker weight in lbs (kg)
Footnotes:
1. Weight does not include shipping pallet.
2. Weight does not include seismic cross braces.
3. Weights are for SDV-R non-arc-resistant
versions. For SDV-R-AR arc-resistant versions,
add 550 lbs (249 kg).