8. Configuration
The switching point is independent of the controller setpoint; only the limit value «
AL»
determines the switching point.
Function: Relay is active when measured value > limit value.
Example:
AL
= 50,
HYSt
= 2
Measured value rising: Relay «K6» switches on at 51 °C.
Measured value falling: Relay «K6» switches off at 49 °C.
AL
HYSt
Measured value
7865d07e/0300
Output 4
Like lk7, but inverted switching function.
AL
HYSt
Measured value
7865d08e/0300
Output 4
HYSt
= switching differential
AL
= limit value
ð
Chapter 7 «Parameter settings»
Function Ik7
Function Ik8