44/57
CC1B7865en
05.12.2002
HVAC Products
8. Configuration
G
The setting of the decimal place has an impact
on the parameters that are dependent on the
actual value!
0000
C113
7865p05/0200
Unit address
Address 0
0
0
Address 1
0
1
...
...
Address 99
9
9
Decimal place, unit, Baud rate
No decimal place, degrees Celsius, 9600 Bd
0
One decimal place, degrees Celsius, 9600 Bd
1
No decimal place, degrees Fahrenheit, 9600 Bd
2
One decimal place, degrees Fahrenheit, 9600 Bd
3
No decimal place, degrees Celsius, 19200 Bd ¹)
4
One decimal place, degrees Celsius, 19200 Bd ¹)
5
No decimal place, degrees Fahrenheit, 19200 Bd ¹)
6
One decimal place, degrees Fahrenheit, 19200 Bd ¹)
7
No decimal place, degrees Celsius, 4800 Bd ¹)
8
One decimal place, degrees Celsius, 4800 Bd ¹)
9
No decimal place, degrees Fahrenheit, 4800 Bd ¹)
A
One decimal place, degrees Fahrenheit, 4800 Bd ¹)
b
Signal for out-of-range
Limit comparators OFF
0
Limit comparators ON
1
Factory setting
0
1
1
0
¹) Only with RWF40.0X2B97
8.3 C113 instrument address, dimensional unit, out-of-range
G