22/57
CC1B7865en
05.12.2002
HVAC Products
5. Operating modes
C111: XX1X ... XX3X
Outside sensor
Heating curve slope H
Setting: 0.0 ... 4.0
C112: XX0X
SP1 via buttons
C112: XX1X
SP1 from outside sensor
C111: XXX2
Section 5.4.4 "Exter-
nal setpoint, binary
setpoint shift"
C111: XXX1
Setpoint changeover
C111: XXX0
No function
C111: X1XX ... X5XX
External setpoint
SPL / oLLo
SPH / oLHi
C111
and
C112
are
described in chapter 8
Weather-dependent
setpoint shift:
No
Yes
D2 open
D2 closed
Active setpoint
Setpoint SP1 is entered on the
user level
Section 6.2 "User level"
Connection of binary input D2
Section 4.2 "Assignment of terminals"
7865f03e/1202
1)
1)
¹) Only with RWF40.0X2B97
5.4.2 Setpoint changeover «SP1» / external setpoint