Chapter 5
Certification
RUGGEDCOM WIN7235
Installation Guide
36
EMC and Environmental Type Tests
•
IEC 61850-3
General Requirements
•
IEC 870-2-2
Telecontrol Equipment and Systems – Part 2: Operating Conditions – Section 2: Environmental Conditions
(Climatic, Mechanical and Other Non-Electrical Influences)
•
MIL-STD-810F
Department of Defense Test Method Standard for Environmental Engineering Considerations and Laboratory
Tests – Method 509.4 (Salt Fog)
Section 5.2
EMC and Environmental Type Tests
The RUGGEDCOM WIN7235 has passed the following Electromagnetic Compatibility (EMC) and environmental
tests.
EMC Type Test for IEC 61850-3
Standard
Method
Description
Test Levels
Climatic Environmental Conditions
IEC 60068-2-1
IEC 61850-3 (5.2)
Low Temperature (Operational)
-40 °C (-40 °F), 16 Hour Dwell
IEC 60068-2-2
IEC 61850-3 (5.2)
High Temperature (Operational)
-65 °C (-149 °F), 16 Hour Dwell
IEC 60068-2-1
IEC 61850-3 (5.2)
Low Temperature (Storage)
-40 °C (-40 °F), 16 Hour Dwell
IEC 60068-2-2
IEC 61850-3 (5.2)
High Temperature (Storage)
-65 °C (-149 °F), 16 Hour Dwell
IEC 60068-2-30
IEEE 61850-3 (5.2)
Humidity (Operational)
95% at 55 °C (131 °F) for 96 Hours
IEC 60068-2-30
IEEE 61850-3 (5.2)
Humidity (Storage)
95% at 55 °C (131 °F) for 96 Hours
Mechanical Environmental Conditions
IEC 60068-2-27
IEC 61850-3 (5.5)
Shock
30 g (965 ft/s
2
)
IEC 60068-2-6
IEC 61850-3 (5.5)
Vibration
2 g (32 ft/s
2
), 10-150 Hz per Axis
EMC
IEC 61000-4-6
IEC 61850-3
(5.7.1.1)
Conducted Immunity
10 Vrms
IEC 61000-4-5
IEC 61850-3
(5.7.1.2)
Surges Immunity
4 kV L-G
IEC 61000-4-12
IEC 61850-3
(5.7.1.3)
Oscillatory Surge
2.5 kV
IEC 61000-4-4
IEC 61850-3
(5.7.1.4)
Electrical Fast Transients Immunity
4 kV
IEC 61000-4-3
IEC 61850-3 (5.7.2)
Radiated Susceptibility Immunity
20 V/m
IEC 61000-4-16
IEC 61850-3 (5.7.3)
Low Frequency Conducted Susceptibility
30 V, 300 V Continues 3
V, 30 V 15 Hz to 150 kHz
IEC 61000-4-8
IEC 61850-3 (5.7.3)
Magnetic Immunity
100 A/m, 1000 A/m (1 sec)