RUGGEDCOM WIN7235
Installation Guide
Chapter 5
Certification
EMC and Environmental Type Tests
37
Standard
Method
Description
Test Levels
CISPR 22
IEC 61850-3 (5.8)
Radiated Emission
30 MHz to 8 GHz
EN 55022
IEC 61850-3 (5.8)
Conducted Emission
150 kHz to 30 MHz
EMC Immunity Type Tests for IEEE 1613
Standard
Method
Description
Test Levels
Climatic Environmental Conditions
IEC 60068-2-1
IEEE 1613 (4.1.1)
Low Temperature (Operational)
-40 °C (-40 °F), 16 Hour Dwell
IEC 60068-2-2
IEEE 1613 (4.1.1)
High Temperature (Operational)
-65 °C (-149 °F), 16 Hour Dwell
IEC 60068-2-1
IEEE 1613 (4.1.2)
Low Temperature (Storage)
-40 °C (-40 °F), 16 Hour Dwell
IEC 60068-2-2
IEEE 1613 (4.1.2)
Low Temperature (Storage)
85 °C (185 °F), 16 Hour Dwell
IEC 60068-2-30
IEEE 1613 (4.1.3)
Humidity (Storage)
95% at 55 °C (131 °F) for 96 Hours
Mechanical Environmental Conditions
IEEE 1613 (10)
Shock (Drop)
1 m (3.3 ft), 1 Fall per Axis
IEC 60068-2-6
IEEE 1613 (10)
Vibration
2 g (32 ft/s
2
), 10-150 Hz per Axis
Power Input
IEC 61000-4-11
IEEE 1613 (5.1)
Voltage Variations
38.4 to 56 V
EMC
IEC 61000-4-12
IEEE 1613 (7.3.1)
IEEE C37.90.1
Oscillatory SWC
2.5 kV
IEC 61000-4-4
IEEE 1613 (7.3.2)
IEEE C37.90.1
Fast Transient SWC
4 kV
IEC 61000-4-3
IEEE 1613 (8)
IEEE C37.90.2
Radiated Susceptibility Immunity
80 MHz to 1 GHz
20 V/m (unmodulated)
35 V/m (modulated)
IEC 61000-4-2
IEEE 1613 (9)
IEEE C37.90.3
ESD
8 kV Contact, 15 kV Air
Insulation
IEC 60255-5 (6.1.3)
IEEE 1613 (6.3
HV Impulse
5 kV
IEC 60255-5 (6.1.4)
IEEE 1613 (6.2)
Dielectric
Military Standard Tests
Test
Description
Test Levels
MIL-STD-810F
Salt Fog
Method 509.4