Certification
6.2 EMC and Environmental Type Tests
•
IEC 61850-3
Communication Networks and Systems in Substations – Part 3: General Require-
ments
6.2
EMC and Environmental Type Tests
The RUGGEDCOM RX1501 has passed the following Electromagnetic Compatibility
(EMC) and environmental tests.
EMC Type Test for IEC 61850-3
Test
Description
Test Levels
Severity
Levels
Enclosure Contact
± 8 kV
IEC 61000-4-2
ESD
Enclosure Air
± 15 kV
4
IEC 61000-4-3
Radiated RFI
Enclosure Ports
20 V/m
Signal ports
± 4 kV @ 2.5 kHz
Note
a
DC Power Ports
AC Power Ports
IEC 61000-4-4 Burst (Fast Transient)
Earth ground ports
± 4 kV
4
Signal ports
± 4 kV Line-to-Ground
± 2 kV Line-to-Line
4
DC Power Ports
± 2 kV Line-to-Ground
± 1 kV Line-to-Line
3
IEC 61000-4-5
Surge
AC Power Ports
± 4 kV Line-to-Ground
± 2 kV Line-to-Line
4
Signal ports
DC Power Ports
AC Power Ports
IEC 61000-4-6
Induced (Con-
ducted) RFI
Earth ground ports
10 V
3
100 A/m, continuous
1000 A/m for 1 s
Note
a
IEC 61000-4-8
Magnetic Field
Enclosure Ports
1000 A/m for 1 s
5
IEC 61000-4-11
Voltage Dips
and Interrupts
AC Power Ports
30% for 1 period
60% for 50 periods
Signal ports
DC Power Ports
IEC 61000-4-12 Damped Oscillatory
AC Power Ports
2.5 kV common, 1 kV dif-
ferential mode @1 MHz
3
Signal ports
IEC 61000-4-16
Mains Frequen-
cy Voltage
DC Power Ports
30 V Continuous
300 V for 1 s
4
IEC 61000-4-17
Ripple on DC
Power Supply
DC Power Ports
10%
3
RUGGEDCOM RX1501
Installation Manual, 05/2020, C79000-G8976-1054-17
55