Chapter 6
Certification
RUGGEDCOM RX1100P
Installation Guide
44
Cellular Modem Certifications
Test
Description
Test Levels
AC Power ports
2.5 kV common and
differential mode @ 1 MHz
Signal ports
5 kV (Failsafe Relay)
DC Power ports
5 kV
IEEE C37.90
HV Impulse
AC Power ports
5 kV
Signal ports
2 kVAC (Failsafe Relay)
DC Power ports
2 kVAC
IEEE C37.90
Dielectric Strength
AC Power ports
2 kVAC
Environmental Type Tests
Test
Description
Test Levels
IEC 60068-2-1
Cold Temperature
Test Ad
-40 °C (40 °F), 16 Hours
IEC 60068-2-2
Dry Heat
Test Bd
85 °C (185 °F), 16 Hours
IEC 60068-2-30
Humidity (Damp Heat, Cyclic)
Test Db
95% (non-condensing),
55 °C (131 °F), 6 cycles
IEC 60255-21-1
Vibration
2 g @ 10-150 Hz
IEC 60255-21-2
Shock
30 g @ 11 ms
Section 6.5
Cellular Modem Certifications
Certification
Standard
Safety
UL 60950-1
cUL 60950-1
EN 60950-1
AS/NZS 6950:2000
EMC
FCC Part 2, 15, 22, 24
EN 55022
EN 55024
Network
PTCRB