Table of Contents

RUGGEDCOM RST2228

Installation Guide

iv

Chapter 4

Communication Ports ...................................................................................... 

25

4.1  SFP Transceivers .........................................................................................................................  25
4.2  Available Modules ....................................................................................................................... 27
4.3  Installing/Removing Modules .......................................................................................................  28

Chapter 5

Technical Specifications ..................................................................................  

31

5.1  Power Supply Specifications ........................................................................................................  31
5.2  Failsafe Alarm Relay Specifications ...............................................................................................  32
5.3  Supported Networking Standards ................................................................................................. 32
5.4  Operating Environment ...............................................................................................................  32
5.5  Mechanical Specifications ............................................................................................................ 33
5.6  Dimension Drawings ...................................................................................................................  33

Chapter 6

Certification ....................................................................................................  

37

6.1  Approvals ...................................................................................................................................  37

6.1.1  CSA ................................................................................................................................. 37
6.1.2  European Union (EU) .......................................................................................................  38
6.1.3  FCC .................................................................................................................................  39
6.1.4  FDA/CDRH ........................................................................................................................ 39
6.1.5  ISED ................................................................................................................................  39
6.1.6  TÜV SÜD .........................................................................................................................  39
6.1.7  RoHS ............................................................................................................................... 39
6.1.8  Other Approvals ............................................................................................................... 40

6.2  EMC and Environmental Type Tests .............................................................................................. 40

Содержание RUGGEDCOM RST2228

Страница 1: ...RUGGEDCOM RST2228 Installation Guide 10 2018 RC1359 EN 04 Preface Introduction 1 Installing the Device 2 Device Management 3 Communication Ports 4 Technical Specifications 5 Certification 6 ...

Страница 2: ...that you regularly check for product updates For the secure operation of Siemens products and solutions it is necessary to take suitable preventive action e g cell protection concept and integrate each component into a holistic state of the art industrial security concept Third party products that may be in use should also be considered For more information about industrial security visit https ww...

Страница 3: ...Gigabit Ethernet 1000Base TX Cabling Recommendations 6 1 5 3 Supported Fiber Optic Cables 6 Chapter 2 Installing the Device 7 2 1 General Procedure 7 2 2 Unpacking the Device 8 2 3 Mounting the Device 8 2 3 1 Mounting the Device to a Rack 9 2 3 2 Mounting the Device to a Panel 10 2 4 Connecting the Failsafe Alarm Relay 11 2 5 Connecting Power 12 2 5 1 Connecting High AC DC Power 13 2 5 2 Connectin...

Страница 4: ...er Supply Specifications 31 5 2 Failsafe Alarm Relay Specifications 32 5 3 Supported Networking Standards 32 5 4 Operating Environment 32 5 5 Mechanical Specifications 33 5 6 Dimension Drawings 33 Chapter 6 Certification 37 6 1 Approvals 37 6 1 1 CSA 37 6 1 2 European Union EU 38 6 1 3 FCC 39 6 1 4 FDA CDRH 39 6 1 5 ISED 39 6 1 6 TÜV SÜD 39 6 1 7 RoHS 39 6 1 8 Other Approvals 40 6 2 EMC and Enviro...

Страница 5: ...cuments Training Customer Support Alerts The following types of alerts are used when necessary to highlight important information DANGER DANGER alerts describe imminently hazardous situations that if not avoided will result in death or serious injury WARNING WARNING alerts describe hazardous situations that if not avoided may result in serious injury and or equipment damage CAUTION CAUTION alerts ...

Страница 6: ...s Siemens to provide training specific to the customer s application For more information about training services and course availability visit https www siemens com ruggedcom or contact a Siemens Sales representative Customer Support Customer support is available 24 hours 7 days a week for all Siemens customers For technical support or general information contact Siemens Customer Support through ...

Страница 7: ...DCOM RST2228 switch is supported by RUGGEDCOM ROS which provides advanced Layer 2 networking functions and advanced cyber security features CONTENTS Section 1 1 Feature Highlights Section 1 2 Description Section 1 3 Required Tools and Materials Section 1 4 Decomissioning and Disposal Section 1 5 Cabling Recommendations Section 1 1 Feature Highlights Extreme Flexibility Support for up to a total of...

Страница 8: ...indicator LEDs for connecting configuring and troubleshooting the device Orientation Options The RUGGEDCOM RST2228 is available in one of two options Option 1 Status panel alarm LED ACO Button CLP port and USB console port are located on the front panel 9 2 1 3 4 5 6 7 8 Figure 1 RUGGEDCOM RST2228 Front Panel Orientation 1 Status Panel 2 ACO Button 3 CLP Port 4 USB Console Port 5 Failsafe Alarm Re...

Страница 9: ...al Block 7 SFP SFP Transceiver Sockets 8 Media Modules 9 Chassis Ground Terminal Key Features Status Panel The status panel displays the real time status of the device 4 1 3 2 5 Figure 3 Status Panel 1 LEDs for 10GBase SFP Transceivers Slot 0 2 LEDs for Module ports 3 Alarm Status LED 4 Power Supply Status LEDs 5 ACO Button LED State Description Solid Link detected Blinking Link activity P number ...

Страница 10: ...ection 2 4 Connecting the Failsafe Alarm Relay Section 5 2 Failsafe Alarm Relay Specifications Power Supply Terminal Block A pluggable terminal block For more information refer to Section 2 5 Connecting Power Section 5 1 Power Supply Specifications Chassis Ground Terminal Protects the device from power surges and accumulated static electricity For information about grounding the device refer to Se...

Страница 11: ...al must be done in accordance with local regulations Section 1 5 Cabling Recommendations Siemens recommends using SIMATIC NET industrial Ethernet shielded cables for all Ethernet ports CONTENTS Section 1 5 1 Protection On Twisted Pair Data Ports Section 1 5 2 Gigabit Ethernet 1000Base TX Cabling Recommendations Section 1 5 3 Supported Fiber Optic Cables Section 1 5 1 Protection On Twisted Pair Dat...

Страница 12: ...liance 5e Yes No action required New installations should be designed with Category 5e or higher 6 Yes No action required 6 Yes Connector and wiring standards to be determined Follow these recommendations for copper data cabling in high electrical noise environments Data cable lengths should be as short as possible preferably 3 m 10 ft in length Copper data cables should not be used for inter buil...

Страница 13: ...ure IMPORTANT This product contains no user serviceable parts Attempted service by unauthorized personnel shall render all warranties null and void Changes or modifications not expressly approved by Siemens Canada Ltd could invalidate specifications test results and agency approvals and void the user s authority to operate the equipment IMPORTANT This product should be installed in a restricted ac...

Страница 14: ...4 Mount the device For more information refer to Section 2 3 Mounting the Device 5 Connect the failsafe alarm relay For more information refer to Section 2 4 Connecting the Failsafe Alarm Relay 6 Connect power to the device and ground the device to safety Earth For more information refer to Section 2 5 Connecting Power 7 Connect the device to the network For more information refer to Chapter 4 Com...

Страница 15: ...her rack or panel hardware installed refer to Section 5 6 Dimension Drawings CONTENTS Section 2 3 1 Mounting the Device to a Rack Section 2 3 2 Mounting the Device to a Panel Section 2 3 1 Mounting the Device to a Rack The RUGGEDCOM RST2228 can be secured to a standard 48 cm 19 in rack using separately purchased rack mount adapters The adapters can be installed at the front or rear of the chassis ...

Страница 16: ...rflow Forced airflow is not required However any increase in airflow will result in a reduction of ambient temperature and improve the long term reliability of all equipment mounted in the rack space 3 Secure the adapters to the rack using M6 or 10 32 screws Section 2 3 2 Mounting the Device to a Panel For panel installations the RUGGEDCOM RST2228 can be ordered with panel adapters for each side o...

Страница 17: ... contact NOTE Control of the failsafe relay output is configurable through RUGGEDCOM ROS One common application for this relay is to signal an alarm if a power failure occurs For more information refer to the RUGGEDCOM ROS User Guide for the RUGGEDCOM RST2228 To connect the failsafe alarm relay do the following 1 Connect the failsafe alarm relay terminal block to the device The terminal block is a...

Страница 18: ...ly Open Terminal 4 Common Terminal 5 Normally Closed Terminal Section 2 5 Connecting Power The RUGGEDCOM RST2228 supports dual redundant AC and or DC power supplies that can be installed in any combination The RUGGEDCOM RST2228 can be equipped with either a screw type or pluggable terminal block which provides power to both power supplies The screw type terminal block is installed using Phillips s...

Страница 19: ...es A socket outlet disconnect device must be installed near the device and be easily accessible Equipment must be installed according to applicable local wiring codes and standards CONTENTS Section 2 5 1 Connecting High AC DC Power Section 2 5 2 Connecting Low DC Power Section 2 5 3 Wiring Examples Section 2 5 1 Connecting High AC DC Power To connect a high AC DC power supply to the device do the ...

Страница 20: ...ure 10 AC Terminal Block Wiring 1 Pluggable Terminal Block 2 Screw Type Terminal Block 3 Positive Line L Terminal for PS1 4 Chassis Ground Terminal for PS1 5 Negative Neutral N Terminal for PS1 6 Positive Line L Terminal for PS2 7 Chassis Ground Terminal for PS2 8 Negative Neutral N Terminal for PS2 3 Connect the ground wire to the chassis ground terminal on the terminal block 4 Connect the Neutra...

Страница 21: ...nection 1 M3 Screw 2 M3 Ring Lug Section 2 5 2 Connecting Low DC Power To connect a low DC power supply to the device do the following NOTE The screw type terminal block is installed using Phillips screws and compression plates allowing either bare wire connections or crimped terminal lugs Use 6 size ring lugs for secure reliable screws which must be removed to make connections CAUTION Electrical ...

Страница 22: ...erminal Block 2 Connect the positive wire from the power source to the positive terminal on the terminal block 1 2 3 4 5 3 4 5 7 8 6 6 7 8 Figure 14 DC Terminal Block Wiring 1 Pluggable Terminal Block 2 Screw Type Terminal Block 3 Positive Terminal for PS1 4 Chassis Ground Terminal for PS1 5 Negative Terminal for PS1 6 Positive Terminal for PS2 7 Chassis Ground Terminal for PS2 8 Negative Terminal...

Страница 23: ...e 15 Assembling the Safety Cover 5 Connect the ground terminal on the power source to the ground terminal on the device 2 1 Figure 16 Chassis Ground Connection 1 M3 Screw 2 M3 Ring Lug Section 2 5 3 Wiring Examples The following illustrate how to connect single and dual power supplies to the device ...

Страница 24: ...Chapter 2 Installing the Device RUGGEDCOM RST2228 Installation Guide 18 Wiring Examples Figure 17 Single High AC DC Power Supply Figure 18 Single Low DC Power Supply ...

Страница 25: ...RUGGEDCOM RST2228 Installation Guide Chapter 2 Installing the Device Wiring Examples 19 Figure 19 Dual High AC DC Power Supply Figure 20 Dual Low DC Power Supply ...

Страница 26: ...Chapter 2 Installing the Device RUGGEDCOM RST2228 Installation Guide 20 Wiring Examples Figure 21 High AC DC Power Supply and Low DC Power Supply ...

Страница 27: ...T2228 USB Console Port Connect a workstation directly to the USB Type B console port to access the boot time control and RUGGEDCOM ROS interfaces The console port provides access to RUGGEDCOM ROS s console and Web interfaces IMPORTANT Console ports are intended to be used only as a temporary connection during initial configuration or troubleshooting NOTE For Microsoft Windows users the RUGGEDCOM U...

Страница 28: ...toring configuration files and or software updates A protective cover is provided to prevent the ingress of dust and dirt when the CLP is not in use CAUTION Mechanical electrical hazard risk of damage to the CLP Do not expose the CLP to extreme temperatures or humidity Do not expose the CLP to large magnetic or static electric fields Do not bend or drop the CLP CAUTION Security hazard risk of unau...

Страница 29: ...ing the CLP 1 CLP 2 Protective cover 2 Insert the protective cover or a new CLP to prevent the ingress of dust and dirt Installing the CLP To install the CLP do the following 1 Remove the protective cover from the CLP port 1 2 Figure 23 Installing the CLP 1 Protective cover 2 CLP 2 Insert the CLP into the CLP port ...

Страница 30: ...Chapter 3 Device Management RUGGEDCOM RST2228 Installation Guide 24 Inserting Removing the CLP ...

Страница 31: ...es at runtime Different types of SFP modules using different integrated MAC and PHY hardware are supported Modules can be installed in any one of the available slots in the device chassis Use RUGGEDCOM ROS to determine which ports are equipped on the device For more information refer to the RUGGEDCOM ROS User Guide for the device 0 1 2 3 4 5 6 Figure 24 RUGGEDCOM RST2228 Fixed Ports and Module Slo...

Страница 32: ...f performance issues related in whole or in part to third party components SFP Transceiver Order Code Speed Mbit s Mode a Nominal Distance km RUGGEDCOM SFP1112 1 6GK6000 8CG01 0AA0 10 100 1000 0 1 RUGGEDCOM SFP1121 1FX2A b 6GK6000 8FE50 0AA0 100 MM 2 RUGGEDCOM SFP1121 1FX2 c 6GK6000 8FE51 0AA0 100 MM 2 RUGGEDCOM SFP1131 1FX20 c 6GK6000 8FE52 0AA0 100 SM 20 RUGGEDCOM SFP1131 1FX50 c 6GK6000 8FE53 0...

Страница 33: ...973 4RJ45 Specifications Ports 4 Port Type RJ45 Speed 10 100 1000 Mbps Interface TX Distance 100 m 328 ft Article Numbers 6GK6297 3RD00 4AB0 Standard 6GK6297 3RD00 4AB1 Conformal Coated RUGGEDCOM RMM2973 4FC Specifications Ports 4 Port Type FastConnect RJ45 Speed 10 100 1000 Mbps Interface TX Distance 100 m 328 ft Article Numbers 6GK6297 3FD00 4AB0 Standard 6GK6297 3FD00 4AB1 Conformal Coated Fibe...

Страница 34: ...AUTION Contamination hazard risk of equipment damage Prevent the ingress of water dirts and other debris that may lead to premature equipment failure Always make sure slots are not left empty and open ports are protected with plugs or covers Removing a Module To remove a media module do the following 1 Make sure power to the device has been disconnected and wait approximately two minutes for any r...

Страница 35: ...he device has been disconnected and wait approximately two minutes for any remaining energy to dissipate 2 Optional If the device is installed in a rack remove it from the rack 3 Remove the current module from the slot 4 Insert the new module into the slot Figure 26 Installing a Module 5 Tighten the screw s to secure the module 6 Optional If necessary install the device in the rack 7 Connect power...

Страница 36: ...Chapter 4 Communication Ports RUGGEDCOM RST2228 Installation Guide 30 Installing Removing Modules ...

Страница 37: ...5 1 Power Supply Specifications NOTE When determining cable lengths make sure the minimum input voltage for the power supply is provided at the power source NOTE Use the internal fuse rating to determine the size of the external circuit breaker fuse Input Range Power Supply Type Terminal Block Type Min Max Internal Fuse Rating Maximum Power Consumption a Wire Gage 12 VDC Single 10 5 VDC 15 VDC 12 ...

Страница 38: ...VLAN Virtual LAN IEEE 802 1p ü ü ü ü Priority levels IEEE 802 1x ü ü ü ü Port based network access control IEEE 802 3 ü 10Base T IEEE 802 3u ü 100Base TX 100Base FX IEEE 802 3z ü 1000Base SX LX IEEE 802 3ab ü 1000Base TX IEEE 802 3ae ü 10GBase IEEE 802 3x ü ü ü ü Full duplex operation Section 5 4 Operating Environment The RUGGEDCOM RST2228 is rated to operate under the following environmental cond...

Страница 39: ...al Specifications 33 Section 5 5 Mechanical Specifications Weight 8 0 kg 18 lbs Ingress Protection IP40 Enclosure Galvanized steel Section 5 6 Dimension Drawings NOTE All dimensions are in millimeters unless otherwise stated 339 4 43 6 337 0 446 0 22 5 Figure 27 Overall Dimensions ...

Страница 40: ...Chapter 5 Technical Specifications RUGGEDCOM RST2228 Installation Guide 34 Dimension Drawings 3 5 6 8 462 2 31 6 23 5 314 0 43 6 285 2 23 5 11 8 297 0 273 5 Figure 28 Rack Mount Dimensions ...

Страница 41: ...RUGGEDCOM RST2228 Installation Guide Chapter 5 Technical Specifications Dimension Drawings 35 3 5 6 8 462 2 31 6 23 5 43 6 285 2 23 5 11 8 297 0 273 5 314 0 Figure 29 Panel Mount Dimensions ...

Страница 42: ...Chapter 5 Technical Specifications RUGGEDCOM RST2228 Installation Guide 36 Dimension Drawings ...

Страница 43: ... Approvals Section 6 2 EMC and Environmental Type Tests Section 6 1 Approvals The following details the approvals issued for the RUGGEDCOM RST2228 CONTENTS Section 6 1 1 CSA Section 6 1 2 European Union EU Section 6 1 3 FCC Section 6 1 4 FDA CDRH Section 6 1 5 ISED Section 6 1 6 TÜV SÜD Section 6 1 7 RoHS Section 6 1 8 Other Approvals Section 6 1 1 CSA This device meets the requirements of the fol...

Страница 44: ...tic compatibility EMC Part 3 3 Limits Limitation of voltage changes voltage fluctuations and flicker in public low voltage supply systems for equipment with rated current 16 A per phase and not subject to conditional connection EN 61000 6 2 Electromagnetic Compatibility EMC Part 6 2 Generic Standards Immunity for Industrial Environments EN 60825 1 Safety of Laser Products Equipment Classification ...

Страница 45: ...not expressly approved by the party responsible for compliance could void the user s authority to operate this device Section 6 1 4 FDA CDRH This device meets the requirements of the following U S Food and Drug Administration FDA standard Title 21 Code of Federal Regulations CFR Chapter I Sub chapter J Radiological Health Section 6 1 5 ISED This device is declared by Siemens Canada Ltd to meet the...

Страница 46: ...olling stock Electronic equipment NEMA TS 2 Traffic Controller Assemblies with NTCIP Requirements Section 6 2 EMC and Environmental Type Tests The RUGGEDCOM RST2228 has passed the following EMC and environmental tests EMC Type Test for IEC 61850 3 NOTE In the case of an all fiber port configuration this product meets all Class 2 requirements Otherwise all Class 1 requirements are met for copper po...

Страница 47: ... 1 s 5 IEC 61000 4 10 Damped Oscillating Magnetic Field Enclosure Ports 100 A m for 1 s 100 kHz and 1 MHz 5 IEC 61000 4 11 Voltage Dips and Interrupts AC Power Ports 30 for 1 period 60 for 50 periods 100 for 5 periods 100 for 50 periods Signal Ports 30 V for 60 s 300 V for 1 s 4 DC Power Ports 30 V for 60 s 300 V for 1 s 4 IEC 61000 4 16 Mains Frequency Voltage AC Power Ports 30 V for 60 s 300 V f...

Страница 48: ...V 2 5 kHz DC Power Ports 4 kV AC Power Ports 4 kV Fast Transient Earth Ground Ports 4 kV Signal Ports 2 5 kV common mode DC Power Ports 2 5 kV common and 1 0 kV Differential Mode Oscillatory AC Power Ports 2 5 kV common and 1 0 kV Differential Mode Signal Ports 5 kV Failsafe Relay DC Power Ports 5 kV HV Impulse AC Power Ports 5 kV Signal Ports 2 kV Failsafe Relay Output DC Power Ports 2 9 kVdc Die...

Страница 49: ...Damp Heat Cyclic Test Db 93 upper temperature 97 lower temperature 55 C 131 F 6 Cycles IEC 60068 2 78 Humidity Damp Heat Steady State Test Cab 10 days 55 C 131 F and 93 Relative Humidity IEC 60255 21 1 Vibration Level 2 2 g 10 to 150 Hz Class 2 Shock Level 2 30 g 11 mS Class 2 IEC 60255 21 2 Bump Level 1 10 g 16 mS Class 1 IEC 60255 21 3 Seismic Method A Class 2 Class 2 IEC 60529 Ingress Protectio...

Страница 50: ...Chapter 6 Certification RUGGEDCOM RST2228 Installation Guide 44 EMC and Environmental Type Tests ...