Certification
6.2 EMC and Environmental Type Tests
Test
Description
Test Levels
Severity
Levels
AC Power
ports
2.5 kV common, 1 kV
differential mode @ 1 MHz
3
Signal ports
30 V Continuous,
300 V for 1 s
4
IEC
61000-4-16
Mains Frequency Voltage
DC Power
ports
30 V Continuous,
300 V for 1 s
4
IEC
61000-4-17
Ripple on DC Power Supply
DC Power
ports
± 15%
4
Signal ports
2 kVAC (Fail-
Safe Relay output)
DC Power
ports
1.5 kV
Dielectric Strength
AC Power
ports
2 kV
Signal ports
5 kV (Fail-Safe
Relay Output)
DC Power
ports
5 kV
IEC 60255-5
HV Impulse
AC Power
ports
5 kV
Siemens specified severity level.
IEEE 1613 EMC Immunity Type Tests
Note
The RUGGEDCOM RS416PF meets Class 2 requirements for an all-fiber configuration
and Class 1 requirements for copper ports.
Description
Test Levels
Enclosure Contact
± 8 kV
ESD
Enclosure Air
± 15 kV
Radiated RFI
Enclosure ports
35 V/m
Signal ports
± 4 kV @ 2.5 kHz
DC Power ports
± 4 kV
AC Power ports
± 4 kV
Fast Transient
Earth ground ports
± 4 kV
Signal ports
2.5 kV common mode @ 1MHz
DC Power ports
2.5 kV common and
differential mode @ 1MHz
Oscillatory
AC Power ports
2.5 kV common and
differential mode @ 1MHz
Signal ports
5 kV (Failsafe Relay)
DC Power ports
5 kV
HV Impulse
AC Power ports
5 kV
Dielectric Strength
Signal ports
2 kVAC (Failsafe Relay)
RUGGEDCOM RS416PF
Installation Manual, 04/2021, C79000-G8976-1355-04
45
Содержание RUGGEDCOM RS416PF
Страница 9: ...Preface Contacting Siemens viii RUGGEDCOM RS416PF Installation Manual 04 2021 C79000 G8976 1355 04 ...
Страница 17: ...Introduction 1 6 3 IEEE 1588 Support 8 RUGGEDCOM RS416PF Installation Manual 04 2021 C79000 G8976 1355 04 ...