Communication Ports
4.4 Serial Ports
Serial DB9 Port with IRIG-B Support
6
9
5
1
Figure 4.10
Serial DB9 Port Pin
Configuration
Mode
Pin
RS232 DTE
RS485
RS422
1
RX-
2
TX/RX+
TX+
3
RX+
4
IRIG-B+
5
Common (Isolated) Ground
6
Common (Isolated) Ground
7
RTS
TX/RX-
TX-
8
CTS
9
Common (Isolated) Ground
Shield
Chassis Ground
In RS232 DTE mode, ports transmit to DTE devices on pin 2 and receive from DTE on pin 3.
Note
Pins 7 and 8 are connected internally. In RS232 mode, these pins enter a high
impedance state. A DTE that asserts RTS will see CTS asserted. However, the device
will not perform hardware flow control.
Serial RJ45 Port
8
1
Figure 4.11
Serial RJ45 Port Pin
Configuration
Pin
RS232
Mode
RS485
Mode
RS422
Mode
1
DSR
RX-
2
DCD
3
DTR
4
Common (Isolated) Ground
5
RX+
6
TXD
TX/RX+
TX+
7
CTS
8
RTS
TX/RX-
TX-
Shield
Chassis Ground
The DSR, DCD and DTR pins are connected together internally.
In RS232 mode, the RJ45 ports conform to EIA-561 DTE, which transmit on TXD and receive on RXD.
Note
Pins 1, 2 and 3 and pins 7 and 8 are connected internally. In RS232 mode, these pins
enter a high impedance state. A DTE that asserts RTS will see CTS asserted. However,
the device will not perform hardware flow control.
30
RUGGEDCOM RS416PF
Installation Manual, 04/2021, C79000-G8976-1355-04
Содержание RUGGEDCOM RS416PF
Страница 9: ...Preface Contacting Siemens viii RUGGEDCOM RS416PF Installation Manual 04 2021 C79000 G8976 1355 04 ...
Страница 17: ...Introduction 1 6 3 IEEE 1588 Support 8 RUGGEDCOM RS416PF Installation Manual 04 2021 C79000 G8976 1355 04 ...
Страница 31: ...Installing Device 2 6 3 Wiring Examples 22 RUGGEDCOM RS416PF Installation Manual 04 2021 C79000 G8976 1355 04 ...