RUGGEDCOM RS416P
Installation Guide
Chapter 2
Installing Device
Connecting AC or DC Power
15
The RUGGEDCOM RS416P can be equipped with either a screw-type or pluggable terminal block, which provides
power to the AC/DC power module and PoE ports. The screw-type terminal block is installed using Phillips screws
and compression plates, allowing either bare wire connections or crimped terminal lugs. Use #6 size ring lugs for
secure, reliable connections under severe shock or vibration.
NOTE
• For 100-240 VAC rated equipment, an appropriately rated AC circuit breaker must be installed.
• For 88-300 VDC rated equipment, an appropriately rated DC circuit breaker must be installed.
• Use minimum #16 gage copper wiring when connecting terminal blocks.
• A circuit breaker is not required for 12, 24 or 48 VDC rated power supplies.
• It is recommended to provide a separate circuit breaker for each power supply module.
• Equipment must be installed according to applicable local wiring codes and standards.
CONTENTS
•
Section 2.6.1, “Connecting AC or DC Power”
•
Section 2.6.2, “Connecting External PoE Power”
•
Section 2.6.3, “Wiring Examples”
Section 2.6.1
Connecting AC or DC Power
To connect a single high AC, high DC or low DC power supply to the device, do the following:
CAUTION!
Electrical hazard – risk of damage to equipment. Before testing the dielectric strength (HIPOT) in the
field, remove the metal jumper. This metal jumper connects transient suppression circuitry to chassis
ground and must be removed in order to avoid damage to transient suppression circuitry during
testing.
CAUTION!
Electrical hazard – risk of damage to equipment. Do not connect AC power cables to a DC power supply
terminal block. Damage to the power supply may occur.
NOTE
Terminals 5 and 7 (POWER 2) are reserved for the external PoE power supply. For information about
connecting the external PoE power supply, refer to
Section 2.6.2, “Connecting External PoE Power”
1. Remove the terminal block cover.
2. Identify the internal power module (POWER 1 or POWER 2) appropriate for the power supply (AC or DC).
3. If a screw-type terminal block is installed, remove the screws from terminals 1 and 3. Use these screws along
with #6 ring lugs to secure the wires to the terminal block.
NOTE
For wiring options, refer to
Section 2.6.3, “Wiring Examples”
.
Содержание RUGGEDCOM RS416P
Страница 4: ...RUGGEDCOM RS416P Installation Guide iv ...
Страница 10: ...Preface RUGGEDCOM RS416P Installation Guide x Customer Support ...
Страница 18: ...Chapter 1 Introduction RUGGEDCOM RS416P Installation Guide 8 IEEE 1588 Support ...
Страница 30: ...Chapter 2 Installing Device RUGGEDCOM RS416P Installation Guide 20 Wiring Examples ...
Страница 48: ...Chapter 5 Technical Specifications RUGGEDCOM RS416P Installation Guide 38 Dimension Drawings ...