Technical data
2015-07-29
Function of inputs
External room temperature sensor, heating/cooling
changeover sensor, operating mode switchover
contact, dewpoint monitor contact, enable electric
heater contact, fault contact, monitoring input,
supply air temperature
Selectable
X1: P38
X2: P40
D1: P42
Switching differential, adjustable
Heating mode
(P30)
Cooling mode
(P31)
2 K (0.5…6 K)
4 °F (1...12 °F)
1 K (0.5…6 K)
2 °F (1...12 °F)
Setpoint setting and setpoint range
Comfort mode
(P08)
Economy mode
(P11-P12)
Protection mode
(P65-P66)
21 °C (5…40 °C)
70 °F (41...104 °F)
15 °C (59 °F)/30 °C (86 °F)
OFF, 5...40 °C (41...104 °F)
8 °C (46 °F)/OFF
OFF, 5...40 °C (41...104 °F)
Multifunctional inputs X1/X2/D1
Input X1
Input X2
Input D1
Selectable
Ext. temperature sensor
(P38=1)
Changeover sensor
(P40=2)
Operating mode switchover
(P42=3)
Built-in room temperature sensor
Measuring range
Accuracy at 25 °C (77 °F)
Temperature calibration range
0…49 °C (32…120 °F)
< ± 0.5 K (± 1 °F)
± 3.0 K (± 6 °F)
Settings and display resolution
Setpoints
Current temperature value displayed
0.5 °C (1 °F)
0.5 °C (1 °F)
Operation
Climatic conditions
Temperature
Humidity
As per IEC 60721-3-3
Class 3K5
0…50 °C (32…122 °F)
<95% r.h.
Transport
Climatic conditions
Temperature
Humidity
Mechanical conditions
As per IEC 60721-3-2
Class 2K3
25…65 °C ( 13…149 °F)
<95% r.h.
Class 2M2
Storage
Climatic conditions
Temperature
Humidity
As per IEC 60721-3-1
Class 1K3
25…65 °C ( 13…149 °F)
<95% r.h.
EU Conformity (CE)
Electronic control type
CE1T3181xx
*)
2.B (micro-disconnection on
operation)
RCM conformity
CE1T3181xx_C1
*)
UL (RDG110U/RDG160TU)
UL 916 PAZX
CSA-C22.2 No. 205 PAZX7
http://database.ul.com
Safety class RDG160T
RDG160TU
II as per EN60730
III as per EN60730
Pollution class
Normal
Degree of protection of housing
IP30 to EN60529
Operational data,
all types
Environmental conditions
Standards