After a power failure, the time of day will blink to indicate power was lost.
However the auto timer will continue to run with the time before the power loss
occurred. Enter the setting mode to adjust the time of day if needed.
The RDG100T, RDG100T/H, and RDG160T.. provide 8 programmable timers A1…A8.
Each timer has a Comfort mode start and end time that can be applied to one or
several weekdays. To set an auto timer, proceed as follows:
1. Press the program mode button twice to select "Auto timer setting" on the
"Programming mode" menu.
2. Turn the rotary knob to the desired timer A1…A8 that you wish to adjust and
press button (OK).
3. Turn the rotary knob to adjust the Comfort mode start time and confirm by
pressing button (OK).
4. Turn the rotary knob to adjust the Comfort mode end time or Economy start time
respectively and confirm by pressing button (OK).
5. Weekday
, and
blink. Press button (OK) to select or button
(Esc) to
deselect each day and advance to the next day.
6. After the 7th day is adjusted, all selected weekdays blink.
Confirm setting for actual timer by pressing button (OK) and advance to the
next timer. To adjust the next timer, repeat step 3…6 or press button (Esc) to
leave the setting mode.
To save your adjustments, remember to press button (OK) in step 6 above before
pressing button (Esc) to leave the programmable timer setting mode.
Auto timer can be disabled via parameter P02 (=3 or 4), (RDG1..T..) or via DIP5 =
ON on RDG160T...
RDG100T..: Time and weekday are always visible on the display, even when auto
timer is OFF (P02 = 3 or 4).
RDG160T..: Time and weekday are NOT visible on the display when auto timer is
disabled, either by setting P02 to 3, 4 or DIP5 to ON.
You can view the 8 timers in sequence:
1. Press the program mode button twice to select the "Auto timer setting" in
programming mode.
2. Turn the rotary knob to review the 8 auto timers.
3. Press
button
(Esc) to return to normal operation.
Power failure
Setting the timers
(RDG1x0T.. only)
Notes
View the programmable
settings