RDG100.., RDG110.., RDG160T.. Basic Documentation
CE1P3181en
Building Technologies
Functions
2015-07-29
4.15.4 Parameters of the "Expert level with diagnostics and test" –
Degree Fahrenheit
P
ar
am
et
er
Name
Factory setting
Range
R
D
G
11
0U
R
D
G
16
0T
U
D
ep
en
d
en
ci
es
Expert level
P30 P-band/switching differential in heating mode
4 °F
1…12 °F
P31 P-band/switching differential in cooling mode
2 °F
1…12 °F
P32 P-band/switching differential for radiator
4 °F
1…12 °F
Appl
P33 Dead zone in Comfort mode
4 °F
1…10 °F
Appl
P34 Setpoint differential (w
D
)
4 °F
1…10 °F
Appl
P35 Integral action time
RDG160TU 45 min.
0…120 min.
x
P46, P47
P36 Heating/cooling changeover switching point cooling
(X1/X2)
61 °F
50…77 °F
P38, P40
P37 Heating/cooling changeover switching point heating
(X1/X2)
82 °F
81…104 °F
P38, P40
P38 Functionality of X1
1 = external sensor
0 = --- (no function)
1 = room temp ext/ret air temp (AI)
2 = H/C changeover (AI/DI)
3 = operating mode contact [DI)
4 = dewpoint sensor (DI)
5 = enable electric heater (DI)
6 = fault input (DI)
9 = Supply air sensor
0..6
0..9
P39 Operating action of X1 if digital input
NO
NO = normally open/open
NC = normally closed/closed
P38
P40 Functionality of X2
2 = H/C changeover
0 = --- (no function)
1 = room temp ext/ret air temp (AI)
2 = H/C changeover (AI/DI)
3 = operating mode contact [DI)
4 = dewpoint sensor. (DI)
5 = enable electric heater (DI)
6 = fault input (DI)
9 = Supply air sensor
0..6
0..9
P41 Operating action of X2 if digital input
NO
NO = normally open/open
NC = normally closed/closed
P40
P42 Functionality of D1
3 = operating mode
changeover
0 = --- (no function)
2 = H/C changeover (DI)
3 = operating mode contact [DI)
4 = dewpoint sensor (DI)
5 = enable electric heater (DI)
6 = fault input (DI)
0..6
0..6
P43 Operating action of D1 if digital input
NO
NO = normally open/open
NC = normally closed/closed
P42
P45 Power of electric heater on Q2 (for adaptive
temperature compensation)
0 kW
0.0…1.2 kW
x
P46 Outputs Y10 (DC) or Q1 (2-pos)
DC 0...10 V (2)
1 = On/Off
2 = DC 0…10V
x
Appl
P47 Outputs Y20 (DC) or Q2 (2.pos)
DC 0...10 V (2)
1 = On/Off
2 = DC 0…10V
x
Appl
P48 Min. output on time
2-position control output
1 min.
1...20 min.
P46
P48 Min. output ON time on Q1, Q2 and Q3, Relay
function P72, P73, P74 ( =2,3,4,5):
1 min.
1...20 min.
x
Appl
P7x
P49 Min. output off time
2-position control output
1 min.
1...20 min.
P47
P49 Min. output OFF time on Q1, Q2 and Q3 Relay
function P72, P73, P74 ( =2,3,4,5):
1 min.
1...20 min.
x
Appl
P7x
P50 Purging function (only when changeover with local
sensor is selected)
OFF
OFF: Not active
1…5 min: Active with selected duration
P38, P40
P51 Floor heating limit temperature
OFF
OFF, 50...122 °F
P38, P40
Parameter available
Parameter not available
P46, P47: Setting to 2-position or 3-position is made with DIP switches 4 and 5.
P45 (RDG160TU) to compensate for heat dissipation of the electric heater relay.
If no sensors or switches are connected, it is not necessary to disable the inputs
(P38, P40 or P42 = no function), the thermostat recognizes if a sensor is connected
(but diagnostic shows "Err").