P01 Control sequence
With 2-pipe/
2-stage:
1 = cooling only
With 4-pipe:
4 = H/C
0 = heating only
1 = cooling only
2 = H/C changeover manually
3 = H/C changeover automatically
4 = heating and cooling
P02 Operating mode profile (operating mode button)
1
1 = (Auto) - Comfort – Protection
2 = (Auto) - Comfort - Economy - Prot
P01
3 = Comfort – Protection
4 = Comfort – Economy – Protection
x
P03 Fan mode selection
0
0 = Auto – Manual
1 = Manual
2 = Auto – Manual – Prot
P52
3 = Auto – Prot
x
P04 Selection of °C or °F
Depends on Wizard setting
0 = degrees Celsius (°C)
1 = degrees Fahrenheit (°F)
P05 Sensor calibration (internally, externally)
0 °F
– 6...6 °F
P06 Standard temperature display
0
0 = room temperature
1 = setpoint
P07 Display info line
(2nd line of LCD)
0
0 = --- (no display)
1 = °C and °F
0..1
x
P08 Comfort setpoint
70 °F
41...104 °F
P09 Min. setpoint for Comfort mode
41 °F
41...104 °F
P10 Max. setpoint for Comfort mode
95 °F
41...104 °F
P11 Economy heating setpoint
59 °F
OFF, 41...WcoolE-saving;
(WcoolE-saving = 104 °F max.)
P12 Economy cooling setpoint
86 °F
OFF, WHeatEco...104 °F;
(WHeatEco = 41 °F min.)
P13 Electric heater in cooling mode
ON
ON: Enabled
OFF: Disabled
Appl
P14 Button lock function
0
0 = unlocked
1 = auto locked
2 = manual locked
P15 Fan stage in dead zone (Comfort)
0
0 = disabled
1 = stage 1 (heating and cooling)
2 = stage 1 (cooling only)
Parameter available
Parameter not available
Parameter display depends on selected application and function.