74/81
Siemens
RDG100.., RDG110.., RDG160T.. Basic Documentation
CE1P3181en
Building Technologies
Technical data
2015-07-29
8 Technical
data
Rated voltage
AC 230 V
Frequency
50/60 Hz
Power consumption RDG100..
RDG110
Max. 8 VA /1 W
Max. 12 VA /2 W
No internal fuse.
External preliminary protection with max. C 10 A circuit breaker
required in all cases.
Fan control Q1, Q2, Q3-N
Rating min, max resistive (inductive)
AC 230 V
AC 5 mA…5(4) A
Fans must NOT be connected in parallel!
Connect one fan directly, for additional fans, one relay for each speed.
Control outputs
Y1, Y2, Y3, Y4-N
RDG100..
Power limitation
AC 230 V, AC 8 mA…1 A
3A fast microfuse, cannot be
exchanged
Y11-N//Y21-N (NO)
RDG110 AC 230 V, AC 5 mA…5(3) A
No internal fuse
External preliminary protection with max. C 10 A circuit breaker in the supply line
required under all circumstances
Multifunctional inputs
X1-M/X2-M
Temperature sensor input
Type
Temperature range
Cable length
Digital input
Operating action
Contact sensing
Parallel connection of several
thermostats for one switch
Insulation against mains
D1-GND
Operating action
Contact sensing
Parallel connection of several
thermostats for one switch
Insulation against mains
NTC (3 k at 25 °C)
0...49 °C
Max. 80 m
Selectable (NO/NC)
DC 0…5 V, max. 5 mA
Max. 20 thermostats per switch.
Do not mix with D1!
N/A, mains potential
Selectable (NO/NC)
SELV DC 6…15 V, 3…6 mA
Max. 20 thermostats per switch.
Do not mix with X1/X2!
3.75 kV, reinforced insulation
Function input
External temperature sensor, changeover sensor,
operating mode switchover contact, dewpoint
monitor contact, enable electric heater contact,
fault contact
Selectable
RDG100../RDG110
Power supply
Outputs
STOP
Note!
Inputs