background image

5/8 

Siemens 

QAX34.1 – Room unit with PPS2 interface 

CA2N1645en_02 

Building Technologies 

 

30 Jun 2009 

Commissioning notes 

After an interrupt of the PPS2 interface the communication will only be re-established 
when the connected controller polls the PPS2 addresses. The duration of the corre-
sponding cycle is: 
RXA: 10 sec; RXB, RXL and RXC: 3 min; PX: 30 sec. 

When the supply voltage is connected (via PPS2 interface) or when the controller initi-
ates a reset, the room unit initially responds as follows: 

Step Function 

Description 

LCD test 

All segments of the display activated for approx. 5 s.  

2 Identification 

by 

controller 

The display reads 

 until the controller identifies the 

room unit as a PPS2 component.  

3 Room 

unit 

ready for opera-
tion 

1 second after identification by the controller, the room 
unit is ready for operation.  

 
If the room unit is connected to a L

ON

M

ARK

-compatible controller (DESIGO RX), the 

display can be used as an aid to commissioning. If the RXT10 commissioning and ser-
vice tool initiates a wink command, the type of controller connected will be displayed on 
the room unit. For example: 

Controller type 

Display 

RXC21.1 

 

RXC30.1 

 

 

Operating notes 

During operation and commissioning, the LCD display also indicates errors, as follows 

Display Description 

Error 

type 

 

C: 

No communication with controller for more than 64 s 
02:  

Firmware version (e.g. Version 2.0) 

 

Room temperature sensor outside range 0 ... 40 °C 

 

Room unit not yet in list of PPS2 components

 

(during 

controller start-up phase) 

 

Controller does not recognize room unit type 

 

Initial value after start-up, before the controller transmits a 
signal 

 

Controller transmits no valid T-value 

 

Static error: The error code remains in the display until the cause of the error has been dealt with. 

Dynamic error: The error code will be displayed instead of the room temperature for 5 s after 
occurrence of the error. The display will then revert to normal. While the error persists, the error 
code will be re-displayed each time the + or – key is operated. The setpoint can be adjusted by 
pressing the key again. 

All other error codes indicate hardware faults. 

 
 
 
 
 

Response on start-up 

Wink function display 
with LON-devices 

Содержание QAX34.1

Страница 1: ...it is used in rooms controlled by an individual room control system to mea sure the room temperature and for operation of the room controller The functions of the LCD display are determined by the controller If manual fan speed control is enabled the room unit is suitable for control of a fan coil system It can also be used in conjunction with a DESIGO PXC automation station 1 The room unit incorp...

Страница 2: ...etpoint adjuster rocker switch for mode selection and fan speed selection plug in connectors and a socket for the commissioning and service tool or service terminal Both the housing and base are made of plastic Base unit Housing 80083 80084 Socket for the commissioning and service tool or service terminal 80166A Room temperature display and sequence heating or cooling Rocker switch for room temper...

Страница 3: ...ress the switch once to switch from a display of the current room temperature to a display of the setpoint Each further operation of the or switch raises or lowers the setpoint by 0 5 K or 1 0 F the unit of measurement is determined by the controller The controller also determines the maximum adjustment range allowed In normal operation the following may be displayed depending on the controller co...

Страница 4: ...oom units may be connected to a PXC automation station they are identified by different settings of their address plugs A twisted pair cable is required for the connection to the controller DESIGO RX uses four core cables DESIGO PX uses two core cables see the respec tive installation guides Screening is not required Mounting The room unit is suitable for wall mounting and for mounting on a recess...

Страница 5: ...ce tool initiates a wink command the type of controller connected will be displayed on the room unit For example Controller type Display RXC21 1 RXC30 1 Operating notes During operation and commissioning the LCD display also indicates errors as follows Display Description Error type C No communication with controller for more than 64 s 02 Firmware version e g Version 2 0 D Room temperature sensor ...

Страница 6: ...IGO RXC CA110334 DESIGO RXB RXL CM110381 DESIGO RXA CA2Z3884 DESIGO PX CA110396 Cable type 2 core or 4 core twisted pairs unscreened Connecting cable for service tool Off the shelf max 3 m Housing protection standard Protection standard to EN 60529 IP 30 Protection class Insulation protection class III Ambient conditions IEC 721 Operation Transport Ambient air conditions Class 3K5 Class 2K3 Temper...

Страница 7: ...voltage CP 1 Device supply Data PPS2 pos CP 2 Device supply Data PPS2 neg Bus connection looped to tool socket C 3 With LONWORKS bus DESIGO RXC CLA C 4 With LONWORKS bus DESIGO RXC CLB 5 8 Not used Standard type RJ45 tool socket 1 3206Z01 2 3 45 67 8 With LONWORKS bus DESIGO RXC CLA With LONWORKS bus DESIGO RXC CLB Not used Not used Not used Not used CP Data PPS2 CP Data PPS2 Connection diagram Ex...

Страница 8: ...ns QAX34 1 Room unit with PPS2 interface CA2N1645en_02 Building Technologies 30 Jun 2009 Dimensions 9 5 32 34 4 2 60 80088 90 100 56 60 56 All dimensions in mm 2000 2009 Siemens Switzerland Ltd Subject to change ...

Отзывы: